HRX-OM-Q026-B
Chapter 5 Display and setting of various functions
HRSH Series
5.20
Alarm customizing function
5-59
29.
Select the changing of DC line fuse cut from the table below with [
▲
] key or [
▼
] key,
and confirm by pressing “SEL”.
Table
5.20-21
List of set value
Set value
Explanation
Initial value
(Default setting)
Operation continues when this alarm signal is
generated.
Operation is stopped when this alarm signal is
generated.
○
How to monitor the temperature alarm Setting and Checking
30.
Press the [SEL] key once.
Setting screen of the temperature alarm monitoring method is displayed on the digital
display.
PV
SV
31.
Select temperature alarm monitoring method from the table below with [
▲
] key or [
▼
]
key, and confirm by pressing “SEL”.
Table
5.20-22
List of set value
Set value
Item
Explanation
Initial value
(Default setting)
Continuous
monitoring
Alarm monitoring starts at the same time as
operation starts.
○
Automatic
monitoring
When the circulating fluid temperature is
outside of the alarm threshold range at the
time of operation start, the alarm will not be
generated until the temperature comes
inside the alarm threshold range.
Monitoring start
timer
Alarm will not be generated until it reaches
the time set for the AS.22 "Monitoring start
timer" after the operation starts.
Alarm monitoring starts when it reaches the
set time.
Automatic
moni
Monitoring start
timer
Alarm will not be generated until it reaches
the time set for the AS.22 "Monitoring start
timer" after the operation starts.
Alarm monitoring starts when it reaches the
set time.
When the circulating fluid temperature
enters the alarm threshold range before it
reaches the set time, the alarm monitoring
will be started at that time.
∗
Settings of this function and example of alarm generating timing for 5.15.3 "Setting of temperature alarm
monitoring method and generation timing".