HRX-OM-Q026-B
Chapter 3 Transport and Setting Up
3.3
Installation
HRSH Series
3-16
Table 3-4 Power supply, contact specifications
Name
Terminal NO.
Specification
5, 6, 7 (DC 24V)
Power supply output
13,14, 15 (24V COM)
DC 24V ±10% 500mA MAX
∗
1
3 (Contact input signal 1)
Contact input signal 1
11 (Common of contact output signal 1)
-Run/stop signal
input
-External switch
signal input
∗
2
4 (Contact input signal 2)
Contact input signal 2
12 (Common of contact output signal 2)
-Run/stop signal
input
-Remote signal
input
-External switch
signal input
∗
2
Switch the
input on the
operation
display panel.
Refer to the
operation
manual
communication
function.
*
1: To use the power of the device, the total load current must be 500mA or less.
If the load is 500mA or more, the internal fuse will be cut to protect the product and the alarm [AL21 DC
line fuse cut] will be generated. Refer to Chapter 6 for handling of alarms.
*
2: Refer to 3.3.6 Wiring of external switch signal input.
1.
Prepare the switch (source voltage: 24V, contact capacity: 35mA or more, min. load
current: 5mA), and cable (3-3 Signal cable).