HRX-OM-Q026-B
Chapter 5 Display and setting of various functions
HRSH Series
5.4
Inspection monitor menu
5-11
Check of the pressure of the lower pressure side of the refrigerant circuit
6.
Press the [SEL] key once.
The pressure of lower pressure refrigerant circuit is displayed on the digital display.
PV
SV
Displays the pressure of the lower pressure side of the refrigerant circuit.
Check of the accumulated operation time of the pump
7.
Press the [SEL] key once.
The accumulated operation time of the pump is displayed on the digital display.
PV
SV
Displays the accumulated operation time of the pump. Refer to the table below for the
display.
Table 5.4-2 List of time display
Cumulative time
Indicated value
0h to
999h
to
1,000h to 99,999h
to
100,000h
Return to
AL28 Pump maintenance alarm is generated when the accumulated operation time of the
pump reaches 20,000 hours (
) or more. For details, refer to Chapter 6 Alarm
indication and trouble shooting
.
Check of the accumulated operation time of the fan
8.
Press the [SEL] key once.
The accumulated operation time of the fun is displayed on the digital display.
PV
SV
Displays the accumulated operation time of the fan. Refer to Table 5.4-2 for the
display.
AL29 Fan maintenance alarm is generated when the accumulated operation time of
the fan motor reaches 30,000 hours (
) or more. For details, refer to Chapter 6
Alarm indication and trouble shooting.
Summary of Contents for HRSH150-A*-20 Series
Page 7: ...HRX OM Q026 B Contents HRSH Series Chapter 9 Product Warranty 9 1...
Page 8: ......
Page 177: ......