5.7
Ready completion (TEMP READY) signal
5-19
5.7 Ready completion (TEMP READY) signal
5.7.1
Ready completion (TEMP READY) signal
This function sets the band width for the circulating fluid set temperature
(upper/lower temperature range) in order to notify the customer by
communication that the circulating fluid temperature has reached the band
range (upper/lower temperature range).The default setting of this function is
“OFF”.
【
Tips
】
This function is available when contact input/output and serial communication
is used. Refer to the Communications Operation Manual for more details.
An example is shown below.
Circulating fluid set temperature
:
20
o
C
READY band width (upper/lower
temperature range)
:
±2
o
C
READY time
:
60 sec.
To be ready is completed 60 seconds after the circulating fluid temperature
reaches 18
o
C to 22
o
C.
Circulating set fluid 20
℃
READY TEMP 22
℃
READY TEMP 18
℃
READY band width
(
upper/lower temperature range
)
2
℃
READY band width
(
upper/lower temperature range
)
2
℃
Circulating set fluid
READY time
60
sec
Completion
of preparation
READY time
lower than
60
sec
Contact output
:
State generation output
Serial
:
ON output
Contact output
:
State not generation output
Serial
:
OFF output
Completion of preparation
(
TEMP READY
)