Fig. 1

HRW***-*  -Y

DI control kit (optional)

Operation Manual

Applicable model: Series HRW

(Thermo Chiller)

- Understand the meaning of the following signs before reading the body of this manual, and keep the instructio

n.

1

Accessory installation

2

Procedure 1

Confirm that a nut, a ferrule, and an insert are installed at the end of the DI tube for IN (Fig. 1).  Insert the DI tu

be

for IN to the end of the DI circuit Supply, and tighten the nut by hand.  At that time, use two spanners, (1) and (2

),

not to rotate the self-align fitting.  Turn the hand-tightened nut by 1/4 rotatio

n.

3

HRX-OM-K018-B

Circulating fluid  Supply

Circulating fluid Return

- It is possible to control the electric resistance of circulating fluid as you like by using an ion exchange resin filt

er

(hereafter DI filter) and electric resistance meter (hereafter DI sensor

).

- DI filter is not attached.  Purchase our HRZ-DF001 separately if you need.  If the DI filter is used at temperature out 

of

the range, 20 to 40degC, also purchase a thermal insulator, HRZ-DF002, to prevent frostbite and a bur

n.

Things to prepare

Spanner (width across flats: (1) 9/16 inch, (2) 1/2 inch, (3) 5/8 inch, (4) 11/16 inch )

DI circuit Supply

(DI tube connecting port for IN)

DI circuit Return

(DI tube connecting port for OUT)

Procedure 4

Supply circulating fluid from IN side of the DI filter to exhaust air.  Continue to supply until OUT side is fill

ed

with circulating fluid.

Fig. 2

Procedure 

3

Mount a therml insulator for DI filter as shown at Fig. 2, and set it in the drain pan (only for the customers who purchas

ed

it).

Procedure 5

Connect the DI tube for OUT and DI tube for IN to OUT side and IN side of the DI filter respectively.  As the 

DI

tube has a strainer and a packing at the DI filter connection part, be careful not to drop them (Refer to Fig. 3

).

Procedure 6

Perform trial operation in accordance with Thermo Chiller operation manual, HRX-OM-K003.  Initially, the 

DI

filter has water.  If ethylene glycol solvent is used, the concentration may be decreased.  Confirm the concentrati

on

after the trial operation.  The proper concentration of ethylene glycol is 60%.  If no leakage is found, install

 a

insulator to a ball valve connected to the DI tube, and fix it with a band 

(Refer to Fig. 4).

Fig. 3

Fig. 4

Introduction

Thank you very much for purchasing DI control kit for our Thermo Chiller, Series HR

W.

This manual is for operators who have enough knowledge for general industrial equipment and devices, and al

so

thoroughly understand assembling, handling, and maintenance of them.  Before assembling, handling, a

nd

maintenance, read and understand this manual and the one for Thermo Chiller, Series HRW carefull

y.

Installing of accessories has to be performed by a customer according to this manua

l.

Refer to the operation manual for Thermo Chiller for warrant

y.

This manual is subject to change without prior notice.

Summary of option

Indication

Meaning

Operator error could result in serious injury or loss of lif

e.

!

Warning

Operator error could result in injury or equipment damage.

Caution

  

Warning

Safety instruction

  

Caution

!

!

- Before using, understand the specification range thoroughly.

 This product is designed as an option for Thermo Chiller, Series HRW.  Do not use this product for the oth

er

purpose, or outside of the specification rang

e.

- Perform installation work without any circulating fluid in Thermo Chiller.

Perform the work before supplying circulating fluid in or after exhausting all the circulating fluid fr

om

Thermo Chiller.  The circulating fluid shoud be exhausted after the fluid gets to be ambient temperatur

e.

Otherwise, an operator may get a burn or frostbite.

- Do not perform installation work while power is on.

Perform lock-out and tag-out of the power securely.  Otherwise, Thermo Chiller may operate unexpectedl

y.

- Understand the contents of this manual and the working procedure thoroughly.

Understand this manual and the one for Thermo Chiller (Document no: HRX-OM-K003) thoroughly.  Ke

ep

this operation manual so that you can refer whenever necessar

y.

- Confirm there is no leakage or condensation after installation.

Confirm there is no leakage or condensation with Thermo Chiller operated.  If leakage is found, stop Ther

mo

Chiller immediately.

- Do not disassemble or modify.

Otherwise it may cause leakage and operation failure.

Introduction

Refer to the accessory list on the back, and confirm the number of the accessory.  In addition, confirm the
model no. plate on the body has "-Y" indication, which is symbol for this option.

DI tube for IN

DI tube for OUT

Nut

Ferrule

Insert

Procedure 2

Confirm that a nut, a ferrule, and a insert are installed at the end of the DI tube for OUT (Fig. 1).  Insert the DI tu

be

for OUT to the end of the DI circuit RETURN, and tighten the nut by hand.  At that time, use two spanners, (3) a

nd

(4), not to rotate the self-align fitting.  Turn the hand-tightened nut by 1/4 rotatio

n.

Indication on the operation display pan el

Status 1

Status 2

Model indication

Menu 1

Maintenance

DI ACC reset

Initial setting 1

Operation panel sequence

Status 3

Setting

(1) Setting of DI SP

Plate a cursor on "DI SP" on the screen "Setting", and press [ENT] key.  Set the value to the one you desi

re

with [    ], [    ], and [    ] keys.  After setting the value, press [ENT] key.

Description

 DI  PV
 DI  SP

 DI  SV

Indication

DI level at the circulating fluid Supply, measured by the DI sens

or

Setting for DI level

Accumulated ON time of the solenoid valve (accumulated fluid-running time through the DI filter)

Status of the solenoid valve (ON=open, OFF=close

d)

 DI  ACC

Operation with operation display pan el

(2) Setting of DI HYS

Set a cursor on "DI HYS" on the screen "Initial setting 4", and press [ENT] key.  Set the value to the one y

ou

desire with [    ], [    ], and [    ] keys.  After setting the value, press [ENT] ke

y.

 DI  HYS

Refer to "DI HYS" below.

(3) Setting of DI level lowering alarm (LOW DI)

Set a cursor on "LOW DI" on the screen "Initial setting 4", and press [ENT] key.  Set the value to the one y

ou

desire with [    ], [    ], and [    ] keys.  After setting the value, press [ENT] key.

 LOW  DI

When the DI level gets lower than the setting, an indication "DI L

OW

LEVEL WRN" will be shown, and a buzzer will be given of

f.

If the setting has "0.0", no alarm will be given of

f.

(4) Reset of DI ACC

Press [    ] and [    ] keys while the screen "DI ACC reset" is shown, and select [YES].  Then, press [ENT] ke

y.

Set range

-

0 to 20Mohm

Yes/No

ON/OFF

0 to 0.9Mohm

0 to 20Mohm

When shipped

from factory

-

0.5Mohm

No

-

0.3Mohm

0.0Mohm

(5) Status of DI circuit

You can confirm it on the screen "Status 3".

External communincati on

Only DI PV can be output by external communication (serial RS-485).  Refer to the separate manua

l,

"Communication Specification/ HRX-PS-K005", for detail. If analog communication (option) is us

ed

refer to "Communication Specification/HRX-PS-K018

".

DI HYS

Solenoid

valve

Operation

condition

DI LEVEL

DI SP

OFF(closed)

ON(open)

Stop

Operation

DI HYS

!

Menu 2

Initial setting 2

Initial setting 3

Initial setting 4

© 2006 SMC CORPORATION All Rights Reserved

1
2

 Thermo Chiller
 HRW□□□-□□-Y
    Rev.□□□
    SMC Co.

TEMP PV    23.8℃

SEL

SEL

SEL

FLOW PV  20.0LPM
PRESS    0.85MPa
R.TEMP     23.8℃

TEMP PV    23.8℃
TEMP SV    25.0℃
OFFSET      0.0℃
OFFSET:      OFF

DI PV      1.0MΩ
DI SP      0.5MΩ
DI ACC        0h
DI SV        OFF

     <MENU>
1.SETTING
2.REMOTE/LOCAL
3.INITIAL SET

     <MENU>
4.MAINTENANCE
5.OPTION

 <MAINTENANCE>
1.DI ACC RESET
2.VALUE OPEN

 <DI ACC RESET>
DI ACC        0h

DATA RESET? No

SEL

ENT

SEL

ENT

   <SETTING>
TEMP SP    25.0℃
DI SP      0.5MΩ

 <INITIAL SET>
OFFSET      0.0℃
OFFSET:      OFF
HIGH TEMP    93℃

 <INITIAL SET>
LOW FLOW    0LPM
FLOW  UNIT   LPM
PRESS UNIT   MPa

 <INITIAL SET>
SLAVE ADRS.  1CH
OUT:         N/A
E OUT:       N/A

 <INITIAL SET>
DI HYS     0.3MΩ
LOW DI     0.0MΩ
F.LOW  TEMP  10℃