Air Dryer
3 Operation / Shutdown
3-3 Shutdown
3
-
2
IDX-OM-I076
IDFA Series
3-3
Shutdown
1) Turn off the Switch with lamp.
2) The lamp will go out and then, the operation will stop.
3-4
Cautions about restart
- Wait at least 3 minutes before restarting the air dryer after it has been shut down. Failure to do this may
cause safety devices to trip due to over load.
If it is not possible to restart, refer to
“Chapter 5 Troubleshooting.”
3-5
Check points before restart
Check following points before you start operation. If any abnormalities occur, immediately stop the
operation. Turn off the Switch with lamp follow by the breaker of the main power supply.
- There are no air leaks.
- Air pressure, temperature, flow rate, and ambient temperature meet the specifications.
- Moisture is being discharged from the drain tube.
- The pointer of evaporating temperature indicates in the green zone.
- Drainage should not be exhausted from the outlet of the air dryer.
- There are no abnormal sound, vibration, or odor.
3-6
Precautions for long-term non-operation
- If the product will not be operated for more than 24 hours, for example at the weekend, turn off the ILS (Switch with
lamp) or power supply, for energy saving and safety. It is also recommended to release the pressure and residual
drainage inside the compressed air piping
and this air dryer.
- The residual drainage in the air dryer may splash over the outlet when the operation is re-started, so it is
recommended to install a filter on the outlet of the air dryer.