COSMOS 302X series servo drives / inverters
Installation, use and maintenance manual - EN
Ver. 1.01
20
5.3.1.1 Mains power
These are the connections of 230VAC supply.
WARNING
AVERTISSEMENT
The power wiring must be made by means of the 5-pole terminal board situated on the container top (see pic-
ture); it is the same for all releases.
These devices are designed for operating with TT or TN distribution systems; the picture shows the recom-
mended wiring diagram:
WARNING
Risk of Electric Shock; wait at least No. 360 seconds (6 minutes) after disconnecting power.
Risque de choc électrique; attendez au moins 360 secondes (6 minutes) après la mise hors
tension.
For safety reasons, the device must always operate with PE (Ground) connected; risk of
electric shock! PE (Ground) connection must be made by means of the specific terminal and
not merely with screws.
230VAC mains power
Label
Signal
L1
230VAC mains – phase 1
L2
230VAC mains – phase 2
LF
NC
PE (Ground)
L1
L2
LF