COSMOS 302X series servo drives / inverters
Installation, use and maintenance manual - EN
Ver. 1.01
24
Protection for UL applications according to IEC / UL 61800-5-1 and C22.2 No.274
The characteristics of the recommended fuses are summarized in the following tables:
5.3.1.1.2 Installation criteria for UL certification
COSMOS 302X
Marking
Mersen
Model
FR10GR69V16
Class
gR (IEC 60269-4)
Dimension
10x38 mm
Rated current
16 A
Working voltage
700V AC
Suitable For Use On A Circuit Capable Of Delivering Not More Than 5000 Arms Symmetri-
cal Amperes, 230 Vac Maximum when protected by semiconductor fuses model
FR10GR69V16 by Mersen.
Integral solid state short circuit protection does not provide branch circuit protection. Branch
circuit protection must be provided in accordance with the Manufacturer Instructions, Na-
tional Electrical Code and any additional local codes.
The drive does not provide Motor Overload protection. External or remote Motor Overload
protection shall be provided in the end-use applications.