HEX390 Installation & Commissioning Instructions September 2016
3
Please Note:
These installation and commission instructions are merely a set of guidelines for effective
installation and setup of the system to yield maximum performance. Actual installation may vary due to
the vast variety of the house architecture and climates. Ensure you fully understand this manual and plan
ahead before commencing the work. Unit must be installed by a suitably qualified person and all electrical
terminations must be carried out by a registered electrician to New Zealand standards.
using maximum of 5 supply outlets for house
floor area not more than 280m
2
10.
The G3 pre-filter must be cleaned or replaced
every 9 months or when necessary.
11.
Isolate electrical supply before commencing
any electrical work.
12.
For return ducts located in open plan living
rooms with inadequate kitchen extraction, or
with smokey log burners, we recommend a
pre-filter (see over page)
13.
In colder areas an auxiliary inline duct heater
is recommended (see over page)
Pre-checks & Recommendations
1.
Before installation, ensure the system suits
your requirements
2.
Check that adequate heat sources are present
for the optimum performance of the system.
3.
Make sure that enough space is available for
the installation of the system.
4.
Plan and mark out the location of the unit and
grilles before commencing
5.
Before cutting holes for diffusers, check that
the penetration is clear of ceiling joists, roof
structure and electrical cabling or plumbing.
6.
For optimum performance, please ensure the
house is well insulated and does not have open
penetrations into the ceiling.
7.
Keep all the duct runs to minimum and avoid
tight bends.
8.
Acoustic ducting (Silentflex) should only be
used on the supply and exhaust sides (not the
return and intake lines).
9.
For optimum performance, please consider
supply
controller
Extract
Fresh Air
Exhaust Air
HEX390