2.4

Functions

• Actuating distance and limit position scanner

The calculation of the available lifting stroke is based on the detection of the 
two limit positions by the SmartDrive MX patented actuating distance scanner. 
The corresponding valve position can be transmitted via the associated 
EnOcean protocol to a master controller/gateway. 

• Battery warning

The moment the battery drops below a critical voltage the SmartDrive MX will 
transmit an error code to a master controller. Furthermore, the battery symbol 
will appear on the display screen. From that moment onwards you have 30 
days left before the batteries need changing.
The symbol for “adapted“ will disappear. You have to readapt the SmartDrive 
MX after a battery replacement by pressing the key (See 5.1)

• Emergency actuating function

 The SmartDrive MX opens the valve 100% as soon as the battery voltage 
drops below a critical value. 

• Internal PI controller

The moment the SmartDrive MX loses continuous radio contact (three times 
wake-up without reception) to its taught controller / gateway the internal PI 
controller will take over and will adjust the temperature according to the set 
temperature value.  A parallel option is local adjustability of target temperature 
by operating the dial.
Additionally, the display screen shows the symbol -><-. A message sent by 
the controller may appear on the smartphone/PC. Simultaneously the 
SmartDrive MX uses the reclaim telegrams to check the availability of the 
controller at every wake-up. The centre will reassume control as soon as 
connection has been re-established.

• Radio interface

The SmartDrive MX comprises an EnOcean radio interface based on 868.3 
MHz, as per ISO/IEC 14543-3-10 featuring extremely low energy 
consumption. The EEP belonging to the SmartDrive MX is A5-20-04.

• Manual setting of target temperature manually

The manual setting option for target temperature is available via the dial at all 
times. As soon as the dial is turned the SmartDrive MX will wake up and show 
the set target value on the display. This temperature is shown for a range of 
10°C to 30°C in 0.5°C steps.

• Room and supply temperature detection 

Supply and room temperature are both detected by an integrated temperature 
sensor. A specially developed correction algorithm clears the measured 
values of other temperature influences. Thus, actual temperature values are 
determined and forwarded for further processing.

• Frost protection

The lowest adjustable target temperature is 10°C. As soon as the actuator has 
been taught and connection to the controller has been established, the room 
temperature will not drop below 10°C. If the actuator detects via the internal 
sensor that the room temperature has dropped below a value of 10°C, the 
controller will receive additional communication. (error telegram 0x14 -> !20).
If radio connection is interrupted permanently, the internal PI controller will 
take over on reaching the temperature threshold of 10°C and control the room 
temperature in such a way that it reaches 10°C.
A precondition for this control is, however, that sufficient heating performance 
is in place.

Summary of Contents for SmartDrive MX

Page 1: ...May 2014 270746 EN driven by excellence INSTALLATION AND OPERATING INSTRUCTIONS SmartDrive MX Snugr is a product of 4INCH sa...

Page 2: ...information SmartDrive MX 2 Version 1 1 May 2014 Installation and operating instructions General information Proof of amendment Version Date Changes 1 0 April 2014 Initial preparation 1 1 May 2014 Re...

Page 3: ...parts 5 2 2 Dimensions 6 2 3 Display 6 2 4 Functions 7 2 5 Data Transfer 9 2 6 Technical data 10 2 7 Environmental conditions 11 3 Transportation Storage 11 4 Assembly 11 4 1 Checking the scope of de...

Page 4: ...thermostat SmartDrive MX described in this document has been designed for room temperature control and adapts the heat supply to the requirements of the individual rooms It is designed exclusively for...

Page 5: ...tocol and boasts a large display screen as well as a dial for conventional manual control Energy supply is provided by two lithium batteries type AA 1 5 V 2 1 Component parts Pos Denomination Explicat...

Page 6: ...ws the target temperature and the error message in large characters and numbers as well as the event symbols table 1 Symbol explanation on page 6 For energy saving reasons display periods are kept sho...

Page 7: ...MX uses the reclaim telegrams to check the availability of the controller at every wake up The centre will reassume control as soon as connection has been re established Radio interface The SmartDriv...

Page 8: ...greater part of its operating time in deep sleep mode so as to keep energy consumption as low as possible You can select the periods for deep sleep mode by using a radio telegram from a selection of...

Page 9: ...rding to EnOcean Smart Acknowledge Standard in order to connect the SmartDrive MX to a controller The following data can be received by the SmartDrive MX Target valve position The target valve positio...

Page 10: ...terface telegram structure Bi directional EnOcean Equipment Profile A5 20 04 Range 30 m inside building dependent on building material Wake up time process and time controlled variable adjustable Tran...

Page 11: ...includes 2 batteries type AA Before you install the SmartDrive MX 4 1 Checking the scope of delivery on page 11 The following sequence of operations is part of the SmartDrive MX 4 2 Insert batteries o...

Page 12: ...from the 06 battery compartment 3 Insert the batteries ATTENTION Do not use rechargeable batteries Do not use rechargeable batteries as their voltage is insufficient When inserting the batteries pay a...

Page 13: ...ons Version 1 1 May 2014 13 4 3 Assembling the SmartDrive MX diagram 5 on page 13 How to assemble the SmartDrive MX 1 Screw the SmartDrive MX threaded connection 04 onto the heating valve 2 Tighten th...

Page 14: ...4 Press and hold the key 01 until the teaching symbol on display of SmartDrive MX appears The SmartDrive MX will then send the teaching telegram to the master central unit 5 Optionally you can set a c...

Page 15: ...reached Replace the batteries 20 Frost protection Temperature has dropped below 10 C Insufficient heating performance Close the window or check the heating system as the case may be 33 Problems with...