background image

11

Socket & See Industrial

www.socketandsee.co.uk

Unit 4, Century Road, High Carr Business Park,

Newcastle, Staffordshire, UK, ST5 7UG

T +44 (0)1782 567096

F +44 (0)1782 567095

© Socket & See Limited (A division of the Kew Technik Group of companies)

Wiring Test

Detects missing E or N (>15k

Ω

)

Detects L-E or L-N swap
Detects Live - Earth/Neutral reversal by use of Polarity Test Pad
Fault indicated by chart on front of instrument
Phase voltage measurement accuracy 1% and displayed on 3 LED’s

<207V AC

LOW

207-253V AC

STANDARD

>253V AC

HIGH

Loop Test

Continuous reading loop resistance (Rl + Re) with result displayed on 5 LED’s
Test current <15mA at 253V AC

Range
<1

Ω

<2

Ω

<20

Ω

<200

Ω

>200

Ω

Each breakpoint has an accuracy of ± 10%
Test stops within 30ms if measured EARTH potential 
>25V AC and ‘Earth Fault’ indication displayed

Environmental

Operating Temperature Range  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0

0

C to 40

0

C

Storage Temperature Range  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -10

0

C to 60

0

C

Operating Humidity  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80% @ 31

0

C to 50% @ 40

0

C

Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140mm x 80mm x 31mm with fixed lead
Weight  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250g

Standards

CE Marked
Complies with BS EN 61010-1: 300V Cat III
Complies with BS EN 61326 (with amendment A1)

Specifications

Summary of Contents for PDL 200A Series

Page 1: ...PDL 200A PDL 234 SERIES MULTIFUNCTION ELECTRICAL TESTERS Tests no trip loop socket mains voltage polarity PDLSERIES U S E R M A N U A L 0 6 0 6...

Page 2: ...notes given on page 8 are for guidance only full reference to the IEE Wiring Regulations must be made l Before use check your tester for any damage to the plug leads and cabinet At Socket See our Eng...

Page 3: ...extremely rare this miswire condition can exist so if your test shows this fault do not proceed if in any doubt advise your customer to contact their supply company immediately FUSE100A FUSE100A From...

Page 4: ...0A and PDL 234 Loop Testers the tester will first go through a brief self check routine and then check that the socket is correctly wired by showing three green green for GO LED s with a continuous to...

Page 5: ...so indicate sequence of test 5 overview 5 5 LED s show Loop Test result 2 Table of correct and common Socket Wiring faults 7 Polarity Test Indications 1 3 LED s show Socket Wiring status 3 3 LED s ind...

Page 6: ...d Your tester is equipped with 2 methods of connecting to a socket or a spur This test lead is used for sockets WARNING you are strongly advised to switch off the MCB or disconnect the fuse feeding th...

Page 7: ...r than 253V AC If the Voltage Range is outside of this standard stop testing your customer should notify their electricity supply company of the problem The Front panel of the tester gives a short rem...

Page 8: ...o seee if it is just tarnished socket contacts or checking where the socket is located if it is the furthest point from the distribution board you may expect it to be a higher reading Less than 100 Oh...

Page 9: ...est LED s should flash GREEN everything is correctly wired including Polarity live and earth neutral are in the right place If the LED s change to RED when you operate the Touch Pad it is possible a v...

Page 10: ...incorrectly wired one or more LED s will go to FLASHING RED to indicate there is a a socket miss wire or other fault If flashing red or orange occurs using the touch pad at this stage this should sho...

Page 11: ...displayed on 3 LED s 207V AC LOW 207 253V AC STANDARD 253V AC HIGH Loop Test Continuous reading loop resistance Rl Re with result displayed on 5 LED s Test current 15mA at 253V AC Range 1 2 20 200 200...

Page 12: ...miswire L N E Warble 6 Faulty N L E miswire NC L N Warble 7 Faulty N E miswire NC N L Warble 8 Faulty N NC E L Warble 9 Faulty N L E reverse NC L E Warble 10 Faulty E L N reverse L NC N Warble 11 Fau...