PDL Series

Loop Test

The 3 Socket Test LED’s will flash ORANGE to indicate a (no-trip)
Loop Measurement Test is being made and unlike other no-trip Loop
Testers the result will be given in a few secconds - if you wish the test
can be repeated to check the result.

For Guidance Only - Refer to the IEE Wiring Standards BS 7671.

1 of 5 LED’s will  illuminate to display the Loop Test result.

Less than 1 Ohm.

< 1

A good result and typical of a correctly wired TN (PME) system.

Less than 2 Ohms.

< 2

A result that would be worth pushing the plug in and out a 
few times to seee if it is just tarnished socket contacts or checking 
where the socket is located - if  it is the furthest point from the 
distribution board you may expect it to be a higher reading.

Less than 100 Ohms.

< 100 Now you must check the wiring system being used - if it is a TT 

system (earth rod) then it is a good result but if it is any other system 
this result should cause concern and urgent investigation is required.

Less than 200 Ohms.

< 200 The same as above, but assuming it is a TT supply system most 

codes of practice accept a Loop Test value of less than 200 Ohms 
for an earth rod for a system protected by a 30mA RCD as being 
acceptable

Greater than 200 Ohms.

> 200 There are very real problems with this system and urgent further 

investigation is required.

Summary of Contents for PDL 200A Series

Page 1: ...PDL 200A PDL 234 SERIES MULTIFUNCTION ELECTRICAL TESTERS Tests no trip loop socket mains voltage polarity PDLSERIES U S E R M A N U A L 0 6 0 6...

Page 2: ...notes given on page 8 are for guidance only full reference to the IEE Wiring Regulations must be made l Before use check your tester for any damage to the plug leads and cabinet At Socket See our Eng...

Page 3: ...extremely rare this miswire condition can exist so if your test shows this fault do not proceed if in any doubt advise your customer to contact their supply company immediately FUSE100A FUSE100A From...

Page 4: ...0A and PDL 234 Loop Testers the tester will first go through a brief self check routine and then check that the socket is correctly wired by showing three green green for GO LED s with a continuous to...

Page 5: ...so indicate sequence of test 5 overview 5 5 LED s show Loop Test result 2 Table of correct and common Socket Wiring faults 7 Polarity Test Indications 1 3 LED s show Socket Wiring status 3 3 LED s ind...

Page 6: ...d Your tester is equipped with 2 methods of connecting to a socket or a spur This test lead is used for sockets WARNING you are strongly advised to switch off the MCB or disconnect the fuse feeding th...

Page 7: ...r than 253V AC If the Voltage Range is outside of this standard stop testing your customer should notify their electricity supply company of the problem The Front panel of the tester gives a short rem...

Page 8: ...o seee if it is just tarnished socket contacts or checking where the socket is located if it is the furthest point from the distribution board you may expect it to be a higher reading Less than 100 Oh...

Page 9: ...est LED s should flash GREEN everything is correctly wired including Polarity live and earth neutral are in the right place If the LED s change to RED when you operate the Touch Pad it is possible a v...

Page 10: ...incorrectly wired one or more LED s will go to FLASHING RED to indicate there is a a socket miss wire or other fault If flashing red or orange occurs using the touch pad at this stage this should sho...

Page 11: ...displayed on 3 LED s 207V AC LOW 207 253V AC STANDARD 253V AC HIGH Loop Test Continuous reading loop resistance Rl Re with result displayed on 5 LED s Test current 15mA at 253V AC Range 1 2 20 200 200...

Page 12: ...miswire L N E Warble 6 Faulty N L E miswire NC L N Warble 7 Faulty N E miswire NC N L Warble 8 Faulty N NC E L Warble 9 Faulty N L E reverse NC L E Warble 10 Faulty E L N reverse L NC N Warble 11 Fau...

Reviews: