7. CONNECTIONS
7.1. Power circuits
For specific networks and power connection diagram possibilities, please refer to page 40.
7.1.1. Cable or bar connections
2A3 2A5 2A7
2A1
2A4 2A6 2A8
2A2
1A3 1A5 1A7
1A1
1A4 1A6 1A8
1A2
Recommended tightening torque:
•
M6: 4,5 N.m
•
M8: 8,3 N.m
•
M10: 20 N.m
•
M12: 40 N.m
Maximum tightening torque:
•
M6: 5,4 N.m
•
M8: 13 N.m
•
M10: 26 N.m
•
M12: 45 N.m
CAUTION
For B3 (8kV)
- Terminations must respect a minimum of 8 mm clearance from live parts to parts
intended to be earthed and between poles
For B4,5,6,7,8 (12kV)
- Terminations must respect a minimum of 14 mm clearance from live parts to
parts intended to be earthed and between poles
7.1.2. Power connection terminals
125 A TO 630 A -
REFER TO SECTION “PRODUCT DIMENSIONS”, PAGE 26 FOR POWER CONNECTION TERMINAL
DETAILS.
33
8.5
8.5
50
33
10
ø 9
ø 15
svr_077_a_1_x_cat
800 A TO 1000 A
16 x 11
60
28.5
15.75
15.75
28.5
15
svr_078_b_1_x_cat
1250 A
15
5
5
12.5
25
25
30
30
45
45
90
ø12.5
1600 A TO 3200 A