ATYS t - 541995C - SOCOMEC
7.1.3. Power connection cross-section
B3
B4
B5
B6
B7
B8
125 A 160 A 200 A 250 A 315 A 400 A 500 A 630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A
Minimum cable
section Cu (mm²)
35
35
50
95
120
185
2x95 2x120 2x185
-
-
-
-
-
-
Recommended
cable section Cu
(mm²), Ith
-
-
-
-
-
-
2x32
x5
2x40
x5
2x50
x5
2x63
x5
2x60
x7
2x100
x5
3x100
x5
2x100
x10
3x100
x10
Maximum cables
section Cu (mm
2
)
50
95
120
150
240
240
2x185 2x300 2x300
4x185
4x185
6x185
-
-
-
Maximum bars
width Cu (mm)
25
25
25
32
32
32
50
50
63
63
63
100
100
100
100
Note for all ratings: Take into account the connection cable lengths and/or others environmental specific operating conditions.