7.4.3. Network
Power inputs (terminals 101-102 & 201-202) are 220/240/277 VAC (208 - 277 VAC) ± 20%. It is necessary to adapt the
power input cable connections according to the network configuration. (Power supply to be taken between phase to phase
or between phase and neutral).
CAUTION
Verify that the power supply between terminals 101 – 102 and 201 – 202 (nominal auxiliary
voltage supply) is within 208-277 VAC ± 20%.
•
Standard kit:
Network 380/415 VAC ± 20% with neutral
conductor (no kit modification required):
•
Kit Modification:
For network 220/240 VAC ± 20%, power supply
cables A-B to connect between phases