59
EN
ATYS t - 541995C - SOCOMEC
10. CHARACTERISTICS
Characteristics according to IEC 60947-3 and IEC 60947-6-1
125 to 630 A
ThermalcurrentI
th
to 40°C
125 A
160 A
200 A
250 A
315 A
400 A
500 A
630 A
Framesize
B3
B3
B3
B4
B4
B4
B5
B5
Rated insulation voltage U
i
(V) (power circuit)
800
800
800
1000
1000
1000
1000
1000
Rated impulse withstand voltage U
imp
(kV) (power circuit)
8
8
8
12
12
12
12
12
Rated insulation voltage U
i
(V) (control circuit)
300
300
300
300
300
300
300
300
Rated impulse withstand voltage U
imp
(kV) (control circuit)
4
4
4
4
4
4
4
4
Rated operational currents I
e
(A) according to IEC 60947-3
Ratedvoltage
Utilisationcategory
A/B
(1)
A/B
(1)
A/B
(1)
A/B
(1)
A/B
(1)
A/B
(1)
A/B
(1)
A/B
(1)
415 VAC
AC-21 A / AC-21 B
125/125
160/160
200/200
250/250
315/315
400/400
500/500
630/630
415 VAC
AC-22 A / AC-22 B
125/125
160/160
200/200
250/250
315/315
400/400
500/500
630/630
415 VAC
AC-23 A / AC-23 B
125/125
160/160
200/200
200/200
315/315
400/400
500/500
500 /630
500 VAC
AC-21 A / AC-21 B
125/125
160/160
200/200
250/250
315/315
400/400
500/500
630/630
500 VAC
AC-22 A / AC-22 B
125/125
160/160
200/200
200/250
200/315
200/400
500/500
500/500
500 VAC
AC-23 A / AC-23 B
80/80
80/80
80/80
200/200
200/200
200/200
400/400
400/400
690 VAC
(3)
AC-21 A / AC-21 B
125/125
160/160
200/200
200/200
200/200
200/200
500/500
500/500
690 VAC
(3)
AC-22 A / AC-22 B
125/125
125/125
125/125
160/160
160/160
160/160
400/400
400/400
690 VAC
(3)
AC-23 A / AC-23 B
63/80
63/80
63/80
125/125
125/125
125/125
400/400
400/400
220 VDC
DC-21 A / DC-21 B
125/125
160/160
200/200
250/250
250/250
250/250
500/500
630/630
220 VDC
DC-22 A / DC-22 B
125/125
160/160
200/200
250/250
250/250
250/250
500/500
630/630
220 VDC
DC-23 A / DC-23 B
125/125
125/125
125/125
200/200
200/200
200/200
500/500
630/630
440 VDC
(2)
DC-21 A / DC-21 B
125/125
125/125
125/125
200/200
200/200
200/200
500/500
630/630
440 VDC
(2)
DC-22 A / DC-22 B
125/125
125/125
125/125
200/200
200/200
200/200
500/500
630/630
440 VDC
(2)
DC-23 A / DC-23 B
125/125
125/125
125/125
200/200
200/200
200/200
500/500
630/630
Rated operational currents I
e
(A) according to IEC 60947-6-1
Ratedvoltage
Utilisationcategory
415 VAC
AC-31 B
125
160
200
250
315
400
500
630
415 VAC
AC-32 B
200
315
400
500
500
415 VAC
AC-33 B
200
200
200
400
400
Current rated as conditional short-circuit with fuse gG DIN, according to IEC 60947-3
Prospective fuse protected short-circuit withstand at 415 VAC(6)
100
100
50
50
50
50
50
50
Prospective fuse protected short-circuit withstand at 690 VAC(kA rms)
50
50
50
50
50
Associated fuse rating (A)
125
160
200
250
315
400
500
630
Short-circuit withstand without protection as per IEC 60947-3
Rated short-time withstand current 0.3s I
cw
at 415 VAC (kA rms)
12
12
12
15
(4)
15
(4)
15
(4)
17
(4)
17
(4)
Rated short-time withstand current 1s I
cw
at 415 VAC (kA rms)
7
7
7
8
(4)
8
(4)
8
(4)
11
(4)
10
(4)
Rated peak withstand current at 415 VAC (kA peak)
20
20
20
30
30
30
45
45
Short-circuit withstand without protection as per IEC 60947-6-1
Rated short-time withstand current 30 ms I
cw
at 415 VAC (kA rms)
10
10
10
10
10
10
Rated short-time withstand current 60 ms I
cw
at 415 VAC (kA rms)
10
12.6
Connection
Minimum Cu cable cross-section as per IEC 60947-1 (mm²)
35
35
50
95
120
185
2 x 95
2 x 120
Recommended Cu busbar cross-section (mm²)
2 x 32 x 5 2 x 40 x 5
Maximum Cu cable cross-section (mm²)
50
95
120
150
240
240
2 x 185
2 x 300
Maximum Cu busbar width (mm)
25
25
25
32
32
32
50
50
Min./max. tightening torque (Nm)
9/13
9/13
9/13
20/26
20/26
20/26
40/45
40/45
Switching time (rated voltage, after receiving command)
Transfer time I-II or II-I (s)
0.85
0.85
0.85
0.9
0.9
0.9
0.95
0.95
I-0 or II-0 (s)
0.55
0.55
0.55
0.5
0.5
0.5
0.55
0.55
Contact transfer time ("black-out" I-II) minimum (s)
0.3
0.3
0.3
0.4
0.4
0.4
0.4
0.4
Power supply
Min./max. power (VAC)
166/332
166/332
166/332
166/332
166/332
166/332
166/332
166/332
Control supply power demand
Demand/rated power (VA) - ATyS r, ATyS d
184/92
184/92
184/92
276/115
276/115
276/115
276/150
276/150
Demand/rated power (VA) - ATyS t, g , p
206/114
206/114
206/114
298/137
298/137
298/137
298/172
298/172
Mechanical specifications
Durability (number of operating cycles)
10,000
10,000
10,000
8,000
8,000
8,000
5,000
5,000
Weight ATyS r 3 P / 4 P (kg)
5.7/ 6.9
5.7/ 6.9
5.7/ 6.9
6.6/ 7.4
6.7/ 7.8
6.7/ 7.8
11.4/ 13.3 11.9/ 14.0
Weight ATyS d 3 P / 4 P (kg)
6.3/ 7.5
6.3/ 7.5
6.3/ 7.5
7.2/ 8.0
7.3/ 8.4
7.3/ 8.4
12.0/ 13.9 12.5/ 14.6
Weight ATyS t, g, p 3 P / 4 P (kg)
6.8/ 8.0
6.8/ 8.0
6.8/ 8.0
7.7/ 8.5
7.8/ 8.9
7.8/ 8.9
12.5/ 14.4 13.0/ 15.1
(1) Category with index A = frequent operation - Category with index B = infrequent operation.
(2) 3-pole device with 2 pole in series for the “+” an 1 pole for the “-”.
4-pole device with 2 poles in series by polarity.
(3) Interphase barriers must be installed on the products.
(4) Values given at 690 VAC.