60
EN
ATYS t - 541995C - SOCOMEC
800 to 3200 A
ThermalcurrentI
th
at 40°C
800 A
1000 A
1250 A
1600 A
2000 A
2500 A
3200 A
Framesize
B6
B6
B6
B7
B8
B8
B8
Rated insulation voltage U
i
(V) (power circuit)
1000
1000
1000
1000
1000
1000
1000
Rated impulse withstand voltage U
imp
(kV) (power circuit)
12
12
12
12
12
12
12
Rated insulation voltage U
i
(V) (control circuit)
300
300
300
300
300
300
300
Rated impulse withstand voltage U
imp
(kV) (control circuit)
4
4
4
4
4
4
4
Rated operational currents I
e
(A) according to IEC 60947-3
Ratedvoltage
Utilisationcategory
A/B
(1)
A/B
(1)
A/B
(1)
A/B
(1)
A/B
(1)
A/B
(1)
A/B
(1)
415 VAC
AC-21 A / AC-21 B
800/800
1000/1000 1250/1250 1600/1600
-/2000
-/2500
-/3200
415 VAC
AC-22 A / AC-22 B
800/800
1000/1000 1250/1250 1600/1600
-/2000
-/2500
-/3200
415 VAC
AC-23 A / AC-23 B
800/800
1000/1000 1250/1250 1250/1250
-/1600
-/1600
-/1600
500 VAC
AC-21 A / AC-21 B
800/800
1000/1000 1250/1250 1600/1600
-/2000
-/2000
-/2000
500 VAC
AC-22 A / AC-22 B
630/630
800/800
1000/1000 1600/1600
500 VAC
AC-23 A / AC-23 B
630/630
630/630
800/800
1000/1000
690 VAC
(3)
AC-21 A / AC-21 B
800/800
1000/1000 1250/1250 1600/1600
-/2000
-/2000
-/2000
690 VAC
(3)
AC-22 A / AC-22 B
630/630
800/800
1000/1000 1000/1000
690 VAC
(3)
AC-23 A / AC-23 B
630/630
630/630
800/800
800/800
220 VDC
DC-21 A / DC-21 B
800/800
1000/1000 1250/1250 1250/1250
220 VDC
DC-22 A / DC-22 B
800/800
1000/1000 1250/1250 1250/1250
220 VDC
DC-23 A / DC-23 B
800/800
1000/1000 1250/1250 1250/1250
440 VDC
(2)
DC-21 A / DC-21 B
800/800
1000/1000 1250/1250 1250/1250
440 VDC
(2)
DC-22 A / DC-22 B
800/800
1000/1000 1250/1250 1250/1250
440 VDC
(2)
DC-23 A / DC-23 B
800/800
1000/1000 1250/1250 1250/1250
Rated operational currents I
e
(A) according to IEC 60947-6-1
Ratedvoltage
Utilisationcategory
415 VAC
AC-31 B
800
1000
1250
1600
2000
2500
3200
415 VAC
AC-32 B
800
1000
1250
1250
2000
2000
2000
415 VAC
AC-33 B
800
1000
1000
1000
1250
1250
1250
Current rated as conditional short-circuit with fuse gG DIN, according to IEC 60947-3
Prospective fuse protected short-circuit withstand at 415 VAC(kA rms)
50
50
100
100
Prospective fuse protected short-circuit withstand at 690 VAC(kA rms)
50
50
50
Associated fuse rating (A)
800
1000
1250
2x800
Short-circuit withstand without protection as per IEC 60947-3
Rated short-time withstand current 0.3s I
cw
at 415 VAC (kA rms)
64
64
64
78
78
78
78
Rated short-time withstand current 1s I
cw
at 415 VAC (kA rms)
35
35
35
50
50
50
50
Rated peak withstand current at 415 VAC (kA peak)
55
55
80
110
120
120
120
Short-circuit withstand without protection as per IEC 60947-6-1
Rated short-time withstand current 30 ms I
cw
at 415 VAC (kA rms)
Rated short-time withstand current 60 ms I
cw
at 415 VAC (kA rms)
20
20
25
32
50
50
50
Connection
Minimum Cu cable cross-section as per IEC 60947-1 (mm²)
2 x 185
Recommended Cu busbar cross-section (mm²)
2 x 50 x 5
2 x 63 x 5
2 x 60 x7
2 x 100 x 5
3 x 100 x 5 2 x 100 x 10 3 x 100 x 10
Maximum Cu cable cross-section (mm²)
4 x 185
4 x 185
4 x 185
6 x 185
Maximum Cu busbar width (mm)
63
63
63
100
100
100
100
Min./max. tightening torque (Nm)
9/13
9/13
20/26
40/45
40/45
40/45
40/45
Switching time (rated voltage, after receiving command)
Transfer time I-II or II-I (s)
2.8
2.8
2.8
2.9
2.8
2.8
2.8
I-0 or II-0 (s)
1.4
1.4
1.4
1.4
1.8
1.8
1.8
Contact transfer time ("black-out" I-II) minimum (s)
1.4
1.4
1.4
1.5
1
1
1
Power supply
Min./max. power (VAC)
166/332
166/332
166/332
166/332
166/332
166/332
166/332
Control supply power demand
Demand/rated power (VA) - ATyS r, ATyS d
460/184
460/184
460/184
460/230
812/322
812/322
812/322
Demand/rated power (VA) - ATyS t, g , p
482/206
482/206
482/206
482/252
834/344
834/344
834/344
Mechanical specifications
Durability (number of operating cycles)
4,000
4,000
4,000
3,000
3,000
3,000
3,000
Weight ATyS r 3 P / 4 P (kg)
27.9/ 32.2 28.4/ 32.9 28.9/ 33.6
33.1/ 39.4
50.7/ 61.6
50.7/ 61.6
61.0/ 75.3
Weight ATyS d 3 P / 4 P (kg)
28.5/ 32.8 29.0/ 33.5 29.5/ 34.2
33.7/ 40.0
51.3/ 62.2
51.3/ 62.2
61.6/ 75.9
Weight ATyS t, g, p 3 P / 4 P (kg)
29.0/ 33.3 29.5/ 34.0 30.0/ 34.7
34.2/ 40.5
51.8/ 62.7
51.8/ 62.7
62.1/ 76.4
(1) Category with index A = frequent operation - Category with index B = infrequent operation.
(2) 3-pole device with 2 pole in series for the “+” an 1 pole for the “-”.
4-pole device with 2 poles in series by polarity.
(3) Interphase barriers must be installed on the products.
(4) Values given at 690 VAC.