23
EN
ATyS p M - 542935E - SOCOMEC
11.
CONNECTION OF THE POWER CIRCUITS
Source supply side
Hexagonal Metric
Allen size 4
5,0 Nm
10 to
70 mm²
15mm
It is essential to tighten all used terminals, with cables and/or bridging bars, before use.
11.1.
Ratings / cross-sections table of correspondence
40 A
63 A
80 A
100 A
125 A
160 A
Min cable size
recommended (mm
2
)
10
16
25
35
50
50
**Max cable size
recommended (mm
2
)
50
50
50
50
70*
70*
*With extension unit.
** Maximum cable size for rigid cable is 50 mm
2
. For larger terminations use the power connection terminals ref. 1399 4017.
Not compatible with aluminium cables
11.2.
Parallel pole set-up for a 4P device used in single phase
Rating conversion table for use in single phase and two-by-two parallel pole set up.
(Max ambient temperature = 40 °C).
Nominal current rating in three-phase (A)
Nominal current rating in single-phase (2 poles in //) (A)
40
63
63
100
80
125
100
160
125
200
160
250