69
EN
ATyS p M - 542935E - SOCOMEC
13.9.5. Function 6
Dec. address. Hex. address.
No. of words
Designation
Unit
Control
21584
5450
1
Command configuration
0x01: Configure RTE (Back transfer)
0x02: Cancel TOF (Off Load Test)
0x03: Configure TOF (Off Load Test)
0x04: Configure TON (On Load Test)
0x05: Configure EOF (External Off Load)
0x06: Configure EON (External On Load)
0x07: Cancel EOF (External Off Load)
0x08: Cancel EON (External On Load)
0x10: Cancel alarms and faults
0x11: Configure FT1
0x12: Configure FT2
0x13: Configure AL1
0x14: Configure AL2
21585
5451
1
Operating mode configuration
3: Auto
4 : Inhibit
5 : Control
Other: Unchanged
21586
5452
1
Priority configuration
0 : Network
1 : Source
I
2 : Source
II
Other: Unchanged
21587
5453
1
Position configuration
Only available in test mode (address 5451 = 5)
0: None
1 : Position 0
2 : Position I
3 : Position II