ATyS / ATyS r - 541630C - SOCOMEC
4.2.
Quick Start ATyS r Frame B6 to B8 (800A to 3200A)
QUICK START
800 A - 3200 A
STEP 1
1
2
800 A
1000 A
1250 A
1600 A
2000 A
2500 A
3200 A
2x185
-
-
-
-
-
-
2x50x5
2x63x5
2x63x7
2x100x5
3x100x5 2x100x10 3x100x10
4x185
4x185
4x185
6x185
-
-
-
63
63
63
100
100
100
100
M8
M8
M10
M12
M12
M12
M12
73.46
/8.3
73.46
/8.3
177.02
/20
354.04
/40
354.04
/40
354.04
/40
354.04
/40
115.06
/13
115.06
/13
230.13
/26
398.30
/45
398.30
/45
398.30
/45
398.30
/45
ATyS / ATyS
r
Preliminary operations
Check the following upon delivery and after removal of the
packaging:
- Packaging and contents are in good condition.
- The product reference corresponds to the order.
- Contents should include:
Qty 1 x ATyS / ATyS r
Qty 1 x Emergency handle and fixing clip
Quick Start instruction sheet
Warning
Risk of electrocution, burns or injury to persons and /
or damage to equipment.
This Quick Start is intended for personnel trained in the
installation and commissioning of this product. For further
details refer to the product instruction manual available on
the SOCOMEC website.
• This product must always be installed and
commissioned by qualified and approved personnel.
• Maintenance and servicing operations should be
performed by trained and authorised personnel.
• Do not handle any control or power cables connected to
the product when voltage may be, or may become
present on the product, directly through the mains or
indirectly through external circuits.
• Always use an appropriate voltage detection device to
confirm the absence of voltage.
• Ensure that no metal objects are allowed to fall in the
cabinet (risk of electrical arcing).
- For 800 - 3200 A (Uimp = 12 kV). Terminations must respect
a minimum of 14 mm clearance from live parts to parts
intended to be earthed and between poles.
Failure to observe good enginering practises as well as to
follow these safety instructions may expose the user and
others to serious injury or death.
Risk of damaging the device
In case the product is dropped or damaged in any way it is
recommended to replace the complete product.
Accessories
• Bridging bars and connection kits.
• Control voltage transformer (400 VAC 230 VAC).
• DC power supply (12/24 VDC 230 VAC).
• Phase barriers.
• Terminal shrouds.
• Terminal screens.
• Auxiliary contacts (Additional).
• Padlocking in 3 positions (I - O - II).
• Lockout accessories (RONIS - EL 11 AP).
• Door escutcheon frame.
• ATS controller ATyS C25.
• ATS controller ATyS C55 or C65.
For further details refer to the product instruction manual
under chapter "Spares and Accessories"
www.socomec.com
To download, brochures, catalogues
and technical manuals:
https://www.socomec.com/
operating-instructions_en.html
549614D
Motorised Source Changeover Switch
EN
Installation and Commissioning
STEP 1
Cabinet / Back Plate
Installation
STEP 3
COMMAND /
CONTROL terminal
connections
STEP 2
Connecting the
POWER section
STEP 4
Power SUPPLY
terminal
connections
STEP 5
CHECK
STEP 6A
Control by an external
order (AUTO)
STEP 6C
Padlocking
STEP 6B
Emergency Manual
Operation
STEP 1
Installation
M8 Type Z
M8
Caution: ensure that the
product is installed on a
flat rigid surface.
Recommended
orientation
OK
OK
STEP 2
Power Terminal Connections
FRAME B6
FRAME B7
FRAME B8
Minimum cable section Cu (mm
2
)
Recommended cable section Cu (mm
2
)
Maximum Cu cable cross-section (mm
2
)
Maximum Cu busbar width (mm)
Type of screw
Recommended tightening torque (
lb.in
/N.m)
Maximum tightening torque (
lb.in
/N.m)
To be connected using terminal lugs, rigid or flexable busbars.
Clip for
storage of
the
emergency
handle