16
EN
ATyS / ATyS r - 541630C - SOCOMEC
5.3. Environmental
The ATy
S rproductmeetsthefollowingenvironmentalrequirements:
5.3.1. IP Rating
ø 1 mm
•
IP2XagainstdirectcontactfortheATyS rmotorizationcontrolunit.
• IP2X against direct contact for the power section with the connections in place and when including
suitable, correctly installed incoming and outgoing terminal shields.
• IP 0 for the bare power section without terminal shields in place.
5.3.2. Operating Conditions
5.3.2.1. Temperature
• From -20 to +40°C without derating
• From -20 to +70°C when applying a Kt derating correction factor
Kt: Correction Factor
Temperature
0.9
40°C…50°C
0.8
50°C…60°C
0.7
60°C…70°C
*Simplifiedderatingmethod:Ithu≤IthxKf
*Amoreprecisecalculationmaybedoneforspecificapplications.Shouldthisberequiredpleasecontact
SOCOMEC.
5.3.2.2. Hygrometry
•
80%humiditywithoutcondensationat55°C
•
95%humiditywithoutcondensationat40°C
5.3.2.3. Altitude
• Up to 2000m in altitude without derating
• For higher altitude the Ka correction factors below apply
Ka: Correction Factor
2000 m < A ≤ 3000 m
3000 m < A ≤ 4000 m
Ue
0.95
0.8
Ie
0.85
0.85
5.3.3. Storage Conditions
5.3.3.1. Temperature
• From -40 to +70°C
Summary of Contents for ATyS r
Page 3: ...3 EN ATyS ATyS r 541630C SOCOMEC ...
Page 41: ...41 EN ATyS ATyS r 541630C SOCOMEC 9 CHARACTERISTICS ...
Page 51: ......