37
EN
ATyS / ATyS r - 541630C - SOCOMEC
8.2. Electrical operation
8.2.1. Power supply
TheATyS ristobepoweredbetweenterminals301and302withasupply
within the limits of :
•
208–277Vac±20%(166–332Vac)
•
50/60Hz±10%
Current Input:
•
10mA(Standbymode)
•
15Amax(Switchingmode)
Surge Protection :
• Vin_sg: 4.8KV – 1.2/50µs
Terminal connector:
• Minimum 1.5mm²
•
Maximum2.5mm²
8.2.2. Fixed inputs
8.2.2.1. Description
The ATy
S rincludesfor5offfixedinputsthrougha6pinconnectorinstalled
on the motorisation module. No additional power supply should be used on
these contacts as the inputs MUST be used with the common supply taken
from terminal 317.
The ATy
S rPowerSupply(301-302)mustbeavailabletoactivateinputs
312 to 317.
Pulsedurationforactivationofcontactinputs:≥60ms.
•
Pin312:
Remote Control Mode Enable when closed with 317.
Thiscontactmustbeclosedwith317soastoactivateallcontrolinputsexceptfor313thattakespriorityandisactive
immaterial of the state of input 312. Enabling remote control through 312 activates the remote control inputs whilst
inhibiting the ATS module automation.
•
Pin313:
Position 0 order if closed with 317 when in AUTO.
(Force the switch to the OFF Position)
This is a
“Priority Order Input”
meaning that when closed with 317 it takes priority over all other electrical commands.
The ATy
S rwillremainin0positionaslongasthecontact313–317remainsclosed.Oncethecontactisopenthe
ATy
S risreadytoreceiveneworders.Thiscontactorderisindependentofotherinputsandisalsoenabledwithout312
connected to 317. Impulse duration to activate and start switching to position O is a minimum of 60ms. The product state
will be unavailable.
•
Pin314:
Position II order if closed with 317.
This contact is active with the ATy
S rinAUTmodewithcontact312–317closedand313–317open.Impulseduration
to activate and switch to position II is a minimum of 60ms.
•
Pin315:
Position I order if closed with 317
This contact is active with the ATy
S rinAUTmodewithcontact312–317closedand313–317open.Impulseduration
to activate and switch to position I is a minimum of 60ms.
•
Pin316:
Position 0 order if closed with 317
This contact is active with the ATy
S rinAUTmodewithcontact312–317closedand313–317open.Impulseduration
to activate and switch to position O is a minimum of 60ms. For contactor logic maintain contacts on between terminal 316
and 317.
•
Pin317:
Common
Common supply for inputs 312 to 316