8.2.2.2. Technical data
MOTORISATION MODULE
Input Qty
5
DirectCurrentIin
0.35 to 0.5mA
Line resistance
1kΩ
Line length
100m(Min.wire1.5mm²#16AWG)
Pulse duration
60ms
Power per Input
0.06VA
Surgeprotection Vin_sg
4.8kV(1.2/50µssurge)
ESDwithstandvoltage(Contact/air)
2/4kV
Insulation(Commonmode)
4.8kVAC
(BetweenI/Pandallcommonparts)
Terminal connector
1.5mm²minimum/2.5mm²max
8.2.2.3. Remote control logic
RemoteswitchingoperationcanbedriveninAUTmodebyexternalvoltfreecontactsasdescribedaboveusinginput
contacts 312 to 317.
DependingonthewiringconfigurationtherearetwotypesoflogicthatmaybeappliedtotheAT
y
S r.
• Impulse logic or
• Contactor logic.
In remote control, the ATy
S rinputsgiveprioritytoordersIandIIover0thereforecontactorlogiccanbeimplementedby
simply bridging terminals 316 and 317.
(NOTE:312–317closed/ForceATyS rtoOFFPosition,takespriorityoverallotherordersnomatterofthecontrollogic
used.)
Impulselogic:
The ATy
S risdriventoastableposition(I–O–II)afterreceiving
an impulse order.
• A switching command of at least 60 ms is necessary to
initiate the switching operation.
• Orders I and II have priority over order 0.
Note:Thelogicdiagramsexcludethetransfertimes.
Imp.≥60ms
order I
position I
order 0
position 0
order II
position II
Impulse logic
(Note :Excludespositionswitchingdelays)
ContactorLogic :
The ATy
S risdriventoaspecificposition(IorII)foraslongas
the order is maintained.
•
OrderOismaintained.(Bridge316–317)
• Orders I and II have priority over order 0.
• Orders I and II have equal priority.
(1st order received is held until no longer maintained).
• If order I or II disappears, the device returns to zero position.
(With the power supply available).
maintened
order I
position I
order 0
position 0
order II
position II
Contactor logic
(Note :Excludespositionswitchingdelays)