8. modBuS In SIngLe uPS unIt
taBLe
Start addresses table length in words
modBuS functIon
UPS Identification
0x1100
32
3 read
Date and hours
0x1360
4
3 read
UPS Configurations
0x1120
16
3 read
UNIT Status (64 bits)
0x1143
4
3 read
UNIT Alarm (80 bits)
0x114A
5
3 read
unit measurements
0x1220
96
3 read
controls permission
0x1150
4
3 read
uPS controls
0x1190
4
6 write
8. 1. H
ow
to
rEad
data
The identification, status and alarms tables should be read completely (this means the number of word to read is
equal to the table length).
The measurements table should be read word by word or per group, without exceed the length of the table. (from
0x1220 to 0x127F).
8. 2. i
ncoming
data
strUctUrE
Example of 6 words
1
2
3
4
5
6
7
8
9
10
11
12
mSB 0
lSB 0
mSB 1
lSB 1
mSB 2
lSB 2
mSB 3
lSB 3
mSB 4
lSB 4
mSB 5
lSB 5
word 0
word 1
word 2
word 3
word 4
word 5
b15 b0 b15 b0 b15 b0 b15 b0 b15 b0 b15 b0
S015 S000 S031 S016 S047 S032 S063 S048 S079 S064 S095 S080
a015 a000 a031 a016 a047 a032 a063 a048
m000
m001
m002
m003
m004
m005
12
Delphys green power
- Ref.: IOMDGPJB0910-GB_11
Summary of Contents for DELPHYS BC
Page 47: ......