Page 9 / 28
STATES
0x038n 0x0387
b0
Common S48 ESD
b1
W
O
R
D
3
S49 Generator set active
b2
S50 Auxiliary input 1
X
X
b3
S51 Auxiliary input 2
X
X
b4
S52 Auxiliary input 3
X
X
b5
S53 Auxiliary input 4
X
X
b6
S54 Auxiliary input 5
X
X
b7
S55 Auxiliary input 6
X
X
b8
S56 Automatic Bypass input is synchro. With Ref
b9
S57 Ext. synchro ref (ACS on)
b10
S58 Commissioning code waiting
b11
S59 eco mode forcé
b12
S60 energy saver off
b13
S61 ext. Auto start request
b14
S62
b15
S63
b0
Synoptic S64 Load protected by inverter
X
b1
W
O
R
D
4
S65 Load on Automatic Bypass
X
b2
S66 Load not supplied
X
b3
S67 Load on maintenance Bypass
X
b4
S68 Auto start in progress
X
b5
S69 Maintenance bypass in progress
X
b6
S70 Auxiliary input 7
X
b7
S71 Auxiliary input 8
X
b8
S72 Auxiliary input 9
X
b9
S73 Auxiliary input 10
X
b10
S74 Auxiliary input 11
X
b11
S75 Auxiliary input 12
b12
S76 Maintenance mode
b13
S77 Alerte Preventive maintenance
b14
S78 Unit in stand-by
b15
S79 Energy saver activated
b0
Parallel
S80 Unit 1 operating in //
X
b1
W
O
R
D
5
S81 Unit 2 operating in //
X
b2
S82 Unit 3 operating in //
X
b3
S83 Unit 4 operating in //
X
b4
S84 Unit 5 operating in //
X
b5
S85 Unit 6 operating in //
X
b6
S86
b7
S87
b8
S88
b9
S89
b10
S90
b11
S91
b12
S92
b13
S93
b14
S94
b15
S95