Page 15 / 28
UPS IDENTIFICATION: Address 0x0000, 12 words
CODE
DESCRIPTION
Number of
WORDS
ADDRESS
Type
Remarks
I00
UPS CODE
1 WORD
0x0000
Numeric value
515 = DELPHYS MX
516 = DELPHYS MX elite
I01
UPS Power
1 WORD
0x0001
Numeric value
In kVA * 10
5000 = 500kVA
I02
Module
number
1 WORD
0x0002
Numeric value
1
I03
Serial
number
5 WORDS
0x0003
1 word = 2 ASCII
codes
LSB = 1. char
MSB = 2. char
UPS Code:CCCCCCAaYYYXXXXXXNNn
Code read :aXXXXXXXXn
I04
Reserved
1 WORD
0x0008
0
I05
Reserved
1 WORD
0x0009
0
I06
Reserved
1 WORD
0x000A
0
I07
Reserved
1 WORD
0x000B
0
DATE & HOURS: Address 0x0360, 4 words
CODE
DESCRIPTION
Number of
words
Addresses
Type
Remarks
D00
Minutes /
seconds
1
0x0360
Byte value
MSB = minutes
LSB = seconds
D01
Hours / day
1
0x0361
Byte value
MSB = day
LSB = hours
D02
Month / day
of
week
1
0x0362
Byte value
MSB = month
LSB = day of the week
1=Monday
7=Sunday
D03
year
1
0x0363
00 = 2000
UPS CONFIGURATION: Address 0x00E0, 32 words
Code
Measurements
Unit
Address
REMARKS
T00
Nominal start input voltage
V
0x00E0
T01
Nominal start output
voltage
V
0x00E1
T02
Nominal input frequency
Hz
0x00E2
T03
Nominal output frequency
Hz
0x00E3
T04
Version
value * 100
0x00E4
100 = V1.00
T05
0x00E5
T06
0x00E6
TO7
0x00E7
T08
Nominal battery capacity
Ah * 10
0x00E8
3000 = 300Ah
T09
Number of battery elements
0x00E9
T10
Reserved
0x00EA
Set to 0xFFFF (-1)
T11
Reserved
0x00EB
Set to 0xFFFF (-1)
T12
Reserved
0x00EC
T13
Working mode
Bits field
0x00ED
b0 not used
b1 = with battery
b2 = Gen Set present
b3 = ’energy saver’ enabled
T14
Redundancy level (only in
//)
value
0x00EE
0 = without
1 = N+1
T15
Reserved
0x00EF
100
T16
..
T31
Reserved
0x00F0
0x00FF
Set to 0xFFFF (-1)