Page 16 / 28
STATUS: Address 0x0020, 6 words
CODE
DESCRIPTION
BIT
ADDRESS
REMARKS
S00
Rectifier Input supply present
0
0x0020
S01
Inverter ON
1
0x0020
S02
Rectifier ON
2
0x0020
S03
Load protected by inverter
3
0x0020
S04
Load on automatic bypass
4
0x0020
S05
Load on battery
5
0x0020
S06
Remote controls disable
6
0x0020
0 = controls enabled
S07
Eco-mode ON
7
0x0020
If this function is available
S08
8
0x0020
S09
9
0x0020
S10
10
0x0020
S11
11
0x0020
S12
12
0x0020
S13
13
0x0020
S14
Battery test failed
14
0x0020
S15
Battery near end of backup time
15
0x0020
IMMINENT STOP and end of backup
time
S16
Battery discharged
0
0x0021
S17
Battery OK
1
0x0021
No alarm and battery circuit
closed
S18
2
0x0021
S19
3
0x0021
S20
4
0x0021
S21
5
0x0021
S22
6
0x0021
S23
7
0x0021
S24
8
0x0021
S25
9
0x0021
S26
Bypass input supply present
10
0x0021
S27
Battery charging
11
0x0021
S28
Bypass
input
frequency
out
of
tolerance
12
0x0021
S29
13
0x0021
Set to 1
S30
UPS on parallel system
14
0x0021
= 0 for single unit
S31
15
0x0021
S32
Unit
operating
(available
or
coupled)
0
0x0022
S33
1
0x0022
S34
2
0x0022
S35
3
0x0022
S36
4
0x0022
S37
5
0x0022
S38
External Input 1
6
0x0022
IN1 ADC slot 1 or 2
S39
External Input 2
7
0x0022
IN2 ADC slot 1 or 2
S40
External Input 3
8
0x0022
IN3 ADC slot 1 or 2
S41
External Input 4
9
0x0022
IN1 ADC slot 3
S42
Controls permission table manage
10
0x0022
Set to 1
S43
11
0x0022
S44
12
0x0022
S45
13
0x0022
S46
Operating on Gen Set
14
0x0022
S47
15
0x0022
S48
Maintenance mode active
0
0x0023
S49
End of the fist maintenance period
1
0x0023
S50
2
0x0023
S51
3
0x0023
S52
4
0x0023
S53
5
0x0023
S54
6
0x0023
S55
7
0x0023
S56
8
0x0023
S57
9
0x0023
S58
10
0x0023
S59
11
0x0023
S60
12
0x0023
S61
13
0x0023
S62
14
0x0023
S63
15
0x0023
…/…