Page 19 / 28
MEASUREMENTS: Address 0x0060, up to 48 words
Code Description
Unit
ADDRESSES
REMARKS
M00
Load rate phase1
%
0x0060
M01
Load rate phase 2
%
0x0061
Set to 0xFFFF if one phase
M02
Load rate phase 3
%
0x0062
Set to 0xFFFF if one phase
M03
UPS load rate
%
0x0063
M04
Battery Capacity
%
0x0064
M05
Battery Capacity
Ah*10
0x0065
M06
Input bypass voltage phase 1
V
0x0066
M07
Input bypass voltage phase 2
V
0x0067
Set to 0xFFFF if one phase
M08
Input bypass voltage phase 3
V
0x0068
Set to 0xFFFF if one phase
M09
Output voltage phase 1
V
0x0069
M10
Output voltage phase 2
V
0x006A
Set to 0xFFFF if one phase
M11
Output voltage phase 3
V
0x006B
Set to 0xFFFF if one phase
M12
0x006C
Set to 0xFFFF (-1)
M13
0x006D
Set to 0xFFFF (-1)
M14
0x006E
Set to 0xFFFF (-1)
M15
Output current phase 1
A*10
0x006F
M16
Output current phase 2
A*10
0x0070
Set to 0xFFFF if one phase
M17
Output current phase 3
A*10
0x0071
Set to 0xFFFF if one phase
M18
Input bypass frequency
Hz*10
0x0072
M19
Output frequency
Hz*10
0x0073
M20
Battery voltage (+)
V*10
0x0074
M21
Battery voltage (-)
V*10
0x0075
Set to 0
M22
Ambient Temperature
°C
0x0076
M23
Remaining backup time
Minutes
0x0077
Set when the load is on
battery
M24
Battery current
A*10
0x0078
M25
0x0079
Set to 0xFFFF (-1)
M26
0x007A
Set to 0xFFFF (-1)
M27
0x007B
Set to 0xFFFF (-1)
M28
Rectifier voltage (+)
V
0x007C
M29
Rectifier voltage (-)
V
0x007D
Set to 0
M30
0x007E
Set to 0xFFFF (-1)
M31
0x007F
Set to 0xFFFF (-1)
M32
0x0080
Set to 0xFFFF (-1)
M33
Rectifier input voltage phase 1
V
0x0081
M34
Rectifier input voltage phase 2
V
0x0082
M35
Rectifier input voltage phase 3
V
0x0083
M36
UPS output power
kW*10
0x0084
M37
Output power phase 1
kVA*10
0x0085
M38
Output power phase 2
kVA*10
0x0086
Set to 0xFFFF if one phase
M39
Output power phase 3
kVA*10
0x0087
Set to 0xFFFF if one phase
M40
0x0088
Set to 0xFFFF (-1)
M41
0x0089
Set to 0xFFFF (-1)
M42
0x008A
Set to 0xFFFF (-1)
M43
0x008B
M44
0x008C
M45
0x008D
M46
0x008E
M47
0x008F