Page 22 / 28
STANDARD JBUS/MODBUS tables in parallel system configuration with central bypass (AC)
TABLE
Start addresses
Table length in words
JBUS/MODBUS
FUNCTION
Identification
0x0000
12
3 READ
Configurations
0x00E0
32
3 READ
Date and hours
0x0360
4
3 READ
States CC
( 96 bits)
0x0020
6
3 READ
Alarms CC
( 64 bits)
0x0040
4
3 READ
Measurements CC
0x0060
48 3 READ
States module 1
( 96 bits)
0x1020
6
3 READ
Alarms module 1
( 64 bits)
0x1040
4
3 READ
Measurements module 1
0x1060
48 3 READ
States module 2
( 96 bits)
0x2020
6
3 READ
Alarms module 2
( 64 bits)
0x2040
4
3 READ
Measurements module 2
0x2060
48 3 READ
States module 3
( 96 bits)
0x3020
6
3 READ
Alarms module 3
( 64 bits)
0x3040
4
3 READ
Measurements module 3
0x3060
48 3 READ
States module 4
( 96 bits)
0x4020
6
3 READ
Alarms module 4
( 64 bits)
0x4040
4
3 READ
Measurements module 4
0x4060
48 3 READ
States module 5
( 96 bits)
0x5020
6
3 READ
Alarms module 5
( 64 bits)
0x5040
4
3 READ
Measurements module 5
0x5060
48 3 READ
States module 6
( 96 bits)
0x6020
6
3 READ
Alarms module 6
( 64 bits)
0x6040
4
3 READ
Measurements module 6
0x6060
48 3 READ
Controls permission
0x05C0
2
3 READ
UPS Controls
0x05B0
1
6 WRITE
STANDARD JBUS/MODBUS table in modular parallel system
TABLE
Start addresses
Table length in words
JBUS/MODBUS
FUNCTION
Identification
0x0000
12
3 READ
Configurations UPS
0x00E0
32
3 READ
Date and hours
0x0360
4
3 READ
Output UPS Measurements
0x0060
48 3 READ
States unit 1
( 96 bits)
0x1020
6
3 READ
Alarms unit 1
( 64 bits)
0x1040
4
3 READ
Measurements unit 1
0x1060
48 3 READ
States unit 2
( 96 bits)
0x2020
6
3 READ
Alarms unit 2
( 64 bits)
0x2040
4
3 READ
Measurements unit 2
0x2060
48 3 READ
States unit 3
( 96 bits)
0x3020
6
3 READ
Alarms unit 3
( 64 bits)
0x3040
4
3 READ
Measurements unit 3
0x3060
48 3 READ
States unit 4
( 96 bits)
0x4020
6
3 READ
Alarms unit 4
( 64 bits)
0x4040
4
3 READ
Measurements unit 4
0x4060
48 3 READ
States unit 5
( 96 bits)
0x5020
6
3 READ
Alarms unit 5
( 64 bits)
0x5040
4
3 READ
Measurements unit 5
0x5060
48 3 READ
States unit 6
( 96 bits)
0x6020
6
3 READ
Alarms unit 6
( 64 bits)
0x6040
4
3 READ
Measurements unit 6
0x6060
48 3 READ