JBUS/MODBUS LINK
Serial link 1 and 2 default settings
Baud rate:
9600 bauds
Parity:
NONE
Data:
8 bits
Stop:
1 bit
Slave:
1
The serial link settings can be set from the control panel or from the graphic touch screen.
How to change the serial link settings ?
Available baud rate:
1200 - 2400 - 4800 - 9600 - 19200 bauds
Parity:
EVEN - ODD - NONE
Slave number:
1 to 32
Settings screen of the control panel (last menu)
S E T T I N G 1
b a u d s :
9 6 0 0
p a r i
t y
:
N O N E
s l a v e :
0 0 1
J B U S
L I N K
Select the settings with
Change the value with and
Graphic touch screen:
J
J
B
B
U
U
S
S
/
/
M
M
O
O
D
D
B
B
U
U
S
S
1
settings are linked to the interface located in slot
5
.
J
J
B
B
U
U
S
S
/
/
M
M
O
O
D
D
B
B
U
U
S
S
2
settings are linked to the interface located in slot
6
.
The serial interface should be activated by the CIM or the factory during the UPS commissioning
This mode needs a special configuration code (PLC mode has to be activated via UPS maintenance
tools).