5.2.2.
Introduction to DIRIS Digiware M-70
The DIRIS Digiware M-70 gateway is a master device on the RS485 bus and master on the DIRIS Digiware bus. It is
used as an Ethernet gateway.
The Ethernet port is used to:
•
Communicate over Ethernet in ModbusTCP (max. 32 simultaneous connections) data from meters and power
monitoring devices connected to the Digiware or RS485 port inputs of the DIRIS Digiware M-70.
•
Access real-time and historical measurements in WEBVIEW-M, the visualisation solftware embedded into
the DIRIS Digiware M-70.
•
Communicate over Ethernet using BACnet IP and SNMP protocols data from meters and power monitoring
devices connected to the Digiware or RS485 port inputs of the DIRIS Digiware M-70.
•
Automatically and cyclically export historical measurements via FTP or FTPS.
•
Automatically send alarm notifications via emails (SMTP or SMTPS).
Data logging and visualisation capabilities of the DIRIS Digiware M-70 are explained in the table below:
Consumption curves
Load curves
Trends
Logged data
Energy: kWh, kvarh,
kVAh
Power: kW, kvar, kVA
Average measurements:
U, V, I, P, Q, S, PF,
Temperature...
Compatible products
COUNTIS Exx (all)
DIRIS Axx (all)
DIRIS Bxx (all)
DIRIS Digiware XXX (all)
COUNTIS Eci, COUNTIS E3x/E4x
DIRIS A-30 /A40v3 + MEM / A60/
A80
DIRIS B-30
DIRIS Digiware I-31 / I-61 /I-35 / I-45
/ I-35dc / S-135 / S-Datacenter
DIRIS A-40
DIRIS B-30
DIRIS Digiware I-35 /
I-45 / U-30 / U-31dc /
U-32dc / S-135 /
S-Datacenter
DIRIS A-40
Integration period
configurable from Easy
Config System, 10 min
to 60 min
configurable from Easy Config System,
1 min to 60 min
Data logging duration
1 year with a 60-min integration period.
Proportional for different values:
For example: 3 months with a 15-min integration period.
This applies no matter how many devices (1 to 32) are connected to the M-70. The
level of detail of the log is not linked to the number of devices connected:
Operation
Readings taken every
10 min - 60 min in the
meter/PMD.
The data is recorded in a cache memory on the meter
and then downloaded by the M-70. If communication
is interrupted, the missing data is recovered by the
M-70 once the connection is restored so that recording
continues.
Data backup (in the
event of a loss of
communication between
the M-70 and the meter)
NO
YES (in the meter’s cache memory)
Export to FTP server
YES
YES
YES
WEBVIEW-M access
Specific configuration
Nothing to configure
(data is recorded
automatically).
Load curves must be activated
on the meters (via Easy Config
System).
Load curves are then
automatically downloaded
from the meter’s cache
memory to the M-70.
Trends must be activated
on the meters (via Easy
Config System).
The logs are then
automatically
downloaded from the
meter’s cache memory
to the M-70.