16.5.
BACnet configuration from the embedded webserver
Click on the “Wrench” icon on the top left corner and click on “Protocols”:
Click on the “Field protocols” tab, and under “Communication”, then BACnet, enter BACnet settings:
BACnet activation: activate or disable BACnet IP communication from the M-50/M-70 gateway.
Virtual Network ID: set the virtual Network ID of the M-50/M-70 gateway. It must be unique within the BACnet network.
Main instance ID: set the main Instance ID (100 by default) for the M-50/M-070 gateway. It must be unique within the
BACnet network.