ITYS 1-3 kVA - 551430A - SOCOMEC
12
EN
Product safety
• UPS enclosure IP rating IP20.
• CAUTION
- To reduce the risk of fire, the unit connects only to a circuit
provided with branch circuit overcurrent protection for: 20A rating,
for Tower 3KS models, Type C.
The upstream circuit breaker for Normal AC/Bypass AC must be easily accessible.
• For PERMANENTLY CONNECTED EQUIPMENT, a readily accessible
disconnect device should be placed externally to the equipment
• For PLUGGABLE EQUIPMENT, the socket-outlet should be installed near the
equipment and should be easily accessible
• Check that the indications on the rating plate correspond to your AC powered
system and to the actual electrical consumption of all the equipment to be
connected to the system.
• Never install the system near liquids or in an excessively damp environment.
• Never allow a foreign body to penetrate the system.
• Never block the ventilation grates of the system.
• Never expose the system to direct sunlight or source of heat.
• If the system must be stored prior to installation, storage must be in a dry place.
• The admissible storage temperature range is -25°C to +55°C without batteries,
0°C to +40°C with batteries.
• This UPS can be used in TN/IT/TT power systems.