6
ITYS PRO
10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
2.1-1
Top view
2.1-2
Front view
15 cm
15 cm
40 cm
40 cm
40 cm
40 cm
40 cm
1,5 m
15 cm
15 cm
15 cm
15 cm
15 cm
1,5 m
≥ 80 cm
free area
free area
UPS
or
BATTERY
CABINET
UPS
or
BATTERY
CABINET
UPS
or
BATTERY
CABINET
UPS
or
BATTERY
CABINET
UPS
UPS
2. ENVIROMENTAL REQUIREMENTS AND HANDLING
NOTE!
Before carrying out any operations on the unit read the Safety standards chapter carefully.
2.1. ENVIRONMENTAL
REQUIREMENTS
Install the unit in an equipment room where only skilled technicians have access. The room must be:
• clean and dry;
• of a suitable size;
• free from conductive, inflammable and corrosive items;
• not exposed directly to sunlight.
The floor must support the weight of the unit and guarantee its stability.
The unit is designed for indoor rooms only.
For information regarding ambient temperature, dimensions and weights refer to the Technical specification chapter.
The connections and the UPS breakers need to be accessible from the rear; a space of at least 1.5 meters should be left at the front
of the UPS for maintenance purposes. It is also advisable to ensure that cable connections are sufficiently long and flexible so that
the unit can be extracted during maintenance, if necessary.
A space at least 40 cm must be left at the back for adequate ventilation (see figure 2.1-1 and 2.1-2).
2.2. HANDLING
• The packaging guarantees the stability of the unit during shipping and handling.
• The unit must remain in a vertical position during all shipping and handling operations.
• Ensure that the floor is strong enough to support the weight of the unit.
• Carry the packaged unit as close as possible to the installation site.
The unit MUST be handled by at least two people. The people MUST take position at the sides of the UPS with respect to the
direction of movement.
When moving the unit on even slightly sloping surfaces, use the locking equipment and braking devices to ensure that the unit does
not tip over.