BATTERY CABINET ITYS PRO 10-20 kVA, MASTERYS 10-160 kVA - Ref.: IOMXXXABXX00-EN  01

3.2 SHIPPING AND MOVING

The unit must remain in a vertical position during all shipping and moving operations.
Ensure that the floor is strong enough to support the weight of the unit.

WARNING! HEAVY WEIGHT!
Move the battery cabinet using a fork lift truck, taking the utmost caution at all times.

NOTE: the unit MUST be handled carefully by at least two people.

Avoid moving the unit by putting pressure on the front door.

CAUTION IF DAMAGED: if packaging is crushed, ripped or open such that the inner contents are 
revealed, the equipment should be kept in an isolated area and inspected by a qualified person. 
If the packaging cannot be shipped the contents should be collected promptly, kept apart, and 
the sender or recipient should be contacted.

All packaging must be recycled in compliance with existing legislation in the country where the 
system is installed.

3.2.1 UNPACKING PROCEDURES

Cables

5x12

2x25mm

2

4x16mm

2

1x35mm

2

 +

1x35mm

2

1x70mm

+

1x70mm

2

1x95mm

+

1x95mm

+

1x50mm

2

1x95mm

+

1x95mm

2

 ITYPxxxxxxx2Pxx

x  1

-

-

-

-

-

x  4

x  1

-

 1MBFxxxxxxx4Pxx

-

x  1

-

-

-

-

x  4

x  1

-

 1MBFxxxxxxx2Fxx

-

x  1

-

-

-

-

x  4

x  1

-

 1MBFxxxxxxx4Fxx

-

x  2

-

-

-

-

x  4

x  1

-

 1MBFxxxxxxx2H-1

-

-

x  2

-

-

-

-

-

x  1

 1MBFxxxxxxx20xx

-

-

-

x  1

-

-

-

-

x  1

 1MBFxxxxxxx4Hxx

-

-

-

x  2

-

-

-

-

x  1

 1MBFxxxxxxx2Hxx

-

-

-

x  2

-

-

-

-

x  1

 1MBFxxxxxxx4Mxx

-

-

-

-

x  1

-

-

-

x  1

 1MBFxxxxxxx2Mxx

-

-

-

-

x  1

-

-

-

x  1

 1MBFxxxxxxx0Mxx

-

-

-

-

-

x  1

-

-

x  1

Summary of Contents for ITYS PRO

Page 1: ...BATTERY CABINET ITYS PRO 10 20 kVA MASTERYS 10 160 kVA EN INSTALLATION AND OPERATING MANUAL www socomec com...

Page 2: ......

Page 3: ...CABLE DC CONNECTION 35 11 CONNECTIONS 1MBFXXXXXXX4FXX 38 11 1 FOUR CABLE DC CONNECTION 38 11 2 THREE CABLE DC CONNECTION 39 12 CONNECTIONS 2 X 1MBFXXXXXXX4FXX 42 12 1 FOUR CABLE DC CONNECTION 42 12 2...

Page 4: ...10 20 kVA MASTERYS 10 160 kVA Ref IOMXXXABXX00 EN 01 1 CERTIFICATE AND CONDITIONS OF WARRANTY The SOCOMEC battery cabinet is part of a UPS system For the warranty conditions please refer to the relev...

Page 5: ...guarantee sufficient ventilation refer to Environmental requirements chapter NOTE Install the unit in a technical room with the following features Suitable size Clean Adequately ventilated Maintained...

Page 6: ...d on the battery cabinet data plate are different from those shown on the mimic panel please correct the settings NOTE Use the double insulated cables supplied with the unit to connect the UPS to the...

Page 7: ...eeds to be disposed of it must be given to companies specialising in the disposal of the system s constituent materials NOTE The batteries are toxic waste If the battery cabinet needs to be scrapped i...

Page 8: ...tify the battery room and provide information about possible hazards Signs should be placed outside the battery room in a visible position The installer is responsible for ensuring that the installati...

Page 9: ...cumulators in series creates hazardous voltages Risk of explosion Avoid short circuits Never place tools or metal objects on the accumulators Corrosive liquids electrolyte Read the user instructions c...

Page 10: ...altitude values are listed in the technical specifications table see Technical Specifications Cooling systems may be required to maintain these values The unit must be installed in an environment with...

Page 11: ...inner contents are revealed the equipment should be kept in an isolated area and inspected by a qualified person If the packaging cannot be shipped the contents should be collected promptly kept apart...

Page 12: ...onsibility to check electrical compatibility and the presence of appropriate protection devices between the UPS and the battery cabinet fuses and switches of sufficient capacity to protect the cables...

Page 13: ...Pro 2 P Fuse holder 2 fuses 1 M B F Battery cabinet for Masterys 4 P Fuse holder 4 fuses 2 F Switch disconnector 2 fuse 4 F Switch disconnector 4 fuse 2 H 1 Magnetothermal switch 4 pole 250A 2 0 With...

Page 14: ...ATTERY CABINET 2 BATTERY CABINETS ITYS PRO 10 20 kVA ITYPxxxxxxx2Pxx 1 UPS MASTERYS 10 40 kVA 1MBFxxxxxxx4Pxx 2 1MBFxxxxxxx4Pxx 1MBFxxxxxxx4Pxx 3 UPS UPS MASTERYS 10 80 kVA 1MBFxxxxxxx2Fxx 1MBFxxxxxxx...

Page 15: ...MASTERYS 10 160 kVA Ref IOMXXXABXX00 EN 01 1 BATTERY CABINET 2 BATTERY CABINETS MASTERYS 100 120 kVA 1MBFxxxxxxx4Hxx 8 1MBFxxxxxxx2Hxx 1MBFxxxxxxx20xx 9 UPS UPS MASTERYS 160 kVA 1MBFxxxxxxx4Mxx 10 1M...

Page 16: ......

Page 17: ...ITYPxxxxxxx2Pxx ITYS PRO 10 20kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...

Page 18: ...XXXXXX2PXX NOTE Before carrying out any operations on the unit read the Safety standards chapter carefully 6 1 TWO CABLE DC CONNECTION A cable 1 2 B B B B B LOCKING CABLE CLAMP CABLE CABLE LENGTH COLO...

Page 19: ......

Page 20: ......

Page 21: ...1MBFxxxxxxx4Pxx MASTERYS 10 40kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...

Page 22: ...erations on the unit read the Safety standards chapter carefully 7 1 FOUR CABLE DC CONNECTION A cable 3 4 5 6 B1 B1 B2 B2 B1 B1 B2 B2 LOCKING CABLE CLAMP CABLE CABLE LENGTH COLOUR CABLE SECTION UPS 1M...

Page 23: ...7 2 THREE CABLE DC CONNECTION A cable 1 2 B1 B1 B2 B2 N LOCKING CABLE CLAMP CABLE CABLE LENGTH COLOUR CABLE SECTION UPS 1MBFxxxxxxx4Pxx B1 M10 40Nm A 3500 mm BROWN 1 x 16 mm N B1 M10 40Nm BLUE 1 x 16...

Page 24: ......

Page 25: ...2 x 1MBFxxxxxxx4Pxx MASTERYS 10 40kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...

Page 26: ...e B cable 1 2 3 4 B1 B1 B2 B2 B1 B1 B2 B2 B1 B1 B2 B2 LOCKING CABLE CLAMP CABLE CABLE LENGTH COLOUR CABLE SECTION UPS 1MBFxxxxxxx4Pxx 1MBFxxxxxxx4Pxx B1 B1 M10 40Nm A 3500 mm BROWN 1 x 16 mm B1 B1 M10...

Page 27: ...CABLE LENGTH COLOUR CABLE SECTION UPS 1MBFxxxxxxx4Pxx 1MBFxxxxxxx4Pxx B1 M10 40Nm A 3500 mm BROWN 1 x 16 mm N B1 M10 40Nm BLUE 1 x 16 mm B2 M10 40Nm GREY 1 x 16 mm B2 M10 40Nm BLACK 1 x 16 mm B1 M10...

Page 28: ......

Page 29: ...2 x 1MBFxxxxxxx2Fxx MASTERYS 10 40kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...

Page 30: ...ad the Safety standards chapter carefully 9 1 FOUR CABLE DC CONNECTION A cable B cable 1 2 3 4 5 BLACK GREY BROWN BLUE B B B1 B1 B2 B2 B B LOCKING CABLE CLAMP CABLE CABLE LENGTH COLOUR CABLE SECTION U...

Page 31: ...CTION A cable B cable 1 2 3 B B B B N BLACK GREY BROWN BLUE LOCKING CABLE CLAMP CABLE CABLE LENGTH COLOUR CABLE SECTION UPS 1MBFxxxxxxx2Fxx 1MBFxxxxxxx2Fxx B M10 40Nm B 3500 mm BROWN 1 x 16 mm N B M10...

Page 32: ......

Page 33: ...2 x 1MBFxxxxxxx2Fxx MASTERYS 60 80kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...

Page 34: ...ead the Safety standards chapter carefully 10 1 FOUR CABLE DC CONNECTION A cable B cable 1 2 3 4 B B B1 B1 B2 B2 B B LOCKING CABLE CLAMP CABLE CABLE LENGTH COLOUR CABLE SECTION UPS 1MBFxxxxxxx2Fxx 1MB...

Page 35: ...NECTION A cable B cable 1 2 B B B B N LOCKING CABLE CLAMP CABLE CABLE LENGTH COLOUR CABLE SECTION UPS 1MBFxxxxxxx2Fxx 1MBFxxxxxxx2Fxx B M10 40Nm A 3500 mm BROWN GREY 2 x 16 mm N B M10 40Nm BLUE BLACK...

Page 36: ......

Page 37: ...1MBFxxxxxxx4Fxx MASTERYS 10 80kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...

Page 38: ...ons on the unit read the Safety standards chapter carefully 11 1 FOUR CABLE DC CONNECTION A cable B cable 1 2 3 4 B1 B1 B2 B2 B1 B1 B2 B2 LOCKING CABLE CLAMP CABLE CABLE LENGTH COLOUR CABLE SECTION UP...

Page 39: ...THREE CABLE DC CONNECTION A cable B cable 1 2 N B1 B1 B2 B2 LOCKING CABLE CLAMP CABLE CABLE LENGTH COLOUR CABLE SECTION UPS 1MBFxxxxxxx4Fxx B1 M10 40Nm A B 3500 mm BROWN 2 x 16 mm N B1 M10 40Nm BLUE...

Page 40: ......

Page 41: ...2 x 1MBFxxxxxxx4Fxx MASTERYS 10 80kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...

Page 42: ...C cable D cable 1 2 3 4 B1 B1 B2 B2 B1 B1 B2 B2 B1 B1 B2 B2 LOCKING CABLE CLAMP CABLE CABLE LENGTH COLOUR CABLE SECTION UPS 1MBFxxxxxxx4Fxx 1MBFxxxxxxx4Fxx B1 B1 M10 40Nm A B 3500 mm BROWN 2 x 16 mm...

Page 43: ...ABLE CABLE LENGTH COLOUR CABLE SECTION UPS 1MBFxxxxxxx4Fxx 1MBFxxxxxxx4Fxx B1 B1 M10 40Nm A B 3500 mm BROWN 2 x 16 mm N B1 M10 40Nm BLUE 2 x 16 mm B2 M10 40Nm GREY 2 x 16 mm B2 B2 M10 40Nm BLACK 2 x 1...

Page 44: ......

Page 45: ...1MBFxxxxxxx2H 1 1MBFxxxxxxx20xx MASTERYS 10 80kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...

Page 46: ...MASTERYS 10 160 kVA Ref IOMXXXABXX00 EN 01 13 CONNECTIONS 1MBFXXXXXXX2H 1 1MBFXXXXXXX20XX NOTE Before carrying out any operations on the unit read the Safety standards chapter carefully 1 2 TX20 3 TX...

Page 47: ...ES CABLE LENGTH COLOUR CABLE SECTION UPS 1MBFxxxxxxx2H 1 1MBFxxxxxxx20xx B1 B1 M8 8Nm A 4500 mm RED 1 x 35 mm B1 B1 M8 8Nm BLACK 1 x 35 mm B2 B2 M8 8Nm B 4500 mm RED 1 x 35 mm B2 B2 M8 8Nm BLACK 1 x 3...

Page 48: ...ON A cables B cables C cables 1 2 NOTE before carrying out any operations on the unit read the Safety Standards chapter carefully 3 In 1MBFxxxxxxx2H 1 connect the bus bar between B1 and B2 in the brea...

Page 49: ...LE SECTION UPS 1MBFxxxxxxx2H 1 1MBFxxxxxxx20xx B M8 8Nm A 4500 mm RED 1 x 35 mm N N M8 8Nm BLACK 1 x 35 mm B M8 8Nm B 4500 mm BLACK 1 x 35 mm M8 8Nm B2 M8 20Nm C 4500 mm RED 1 x 70 mm M8 8Nm B2 M8 20N...

Page 50: ...50 EN BATTERY CABINET ITYS PRO 10 20 kVA MASTERYS 10 160 kVA Ref IOMXXXABXX00 EN 01 8 Nm C cables TX20 1 2 3 4 5 C cables M10 25 Nm A B cables 8 Nm TX20...

Page 51: ......

Page 52: ......

Page 53: ...1MBFxxxxxxx4Hxx MASTERYS 100 120kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...

Page 54: ...0 20 kVA MASTERYS 10 160 kVA Ref IOMXXXABXX00 EN 01 14 CONNECTIONS 1MBFXXXXXXX4HXX NOTE Before carrying out any operations on the unit read the Safety standards chapter carefully Do not remove side pa...

Page 55: ...B1 B1 B2 B2 LOCKING CABLE CLAMP CABLE CABLE LENGTH COLOUR CABLE SECTION UPS 1MBFxxxxxxx4Hxx B1 B1 M8 8Nm A 4500 mm RED 1 x 70 mm B1 B1 M8 8Nm BLACK 1 x 70 mm B2 B2 M8 8Nm B 4500 mm RED 1 x 70 mm B2 B...

Page 56: ...ables B cables 1 2 Replace the label B1 with B Replace the label B1 with B Throw away the cable with the label B2 Replace the label B2 with N 3 In 1MBFxxxxxxx4Hxx connect the bus bar between B1 and B2...

Page 57: ...KING CABLE CLAMP CABLE CABLE LENGTH COLOUR CABLE SECTION UPS 1MBFxxxxxxx4Hxx B M8 8Nm A 4500 mm RED 1 x 70 mm N N M8 8Nm BLACK 1 x 70 mm B M8 8Nm B 4500 mm BLACK 1 x 70 mm Close the battery bridge cir...

Page 58: ...58 EN BATTERY CABINET ITYS PRO 10 20 kVA MASTERYS 10 160 kVA Ref IOMXXXABXX00 EN 01 TX20 1 A B cables 8 Nm TX20 2 3...

Page 59: ......

Page 60: ......

Page 61: ...1MBFxxxxxxx2Hxx 1MBFxxxxxxx20xx MASTERYS 100 120kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...

Page 62: ...MASTERYS 10 160 kVA Ref IOMXXXABXX00 EN 01 15 CONNECTIONS 1MBFXXXXXXX2HXX 1MBFXXXXXXX20XX NOTE Before carrying out any operations on the unit read the Safety standards chapter carefully Do not remove...

Page 63: ...CABLE LENGTH COLOUR CABLE SECTION UPS 1MBFxxxxxxx2H 1 1MBFxxxxxxx20xx B1 B1 M8 8Nm A 4500 mm RED 1 x 70 mm B1 B1 M8 8Nm BLACK 1 x 70 mm B2 B2 M8 8Nm B 4500 mm RED 1 x 70 mm B2 B2 M8 8Nm BLACK 1 x 70...

Page 64: ...cables C cables 1 2 Replace the label B1 with B Replace the label B1 with B Throw away the cable with the label B2 Replace the label B2 with N 3 In 1MBFxxxxxxx2Hxx connect the bus bar between B1 and...

Page 65: ...LE SECTION UPS 1MBFxxxxxxx2Hxx 1MBFxxxxxxx20xx B M8 8Nm A 4500 mm RED 1 x 70 mm N N M8 8Nm BLACK 1 x 70 mm B M8 8Nm B 4500 mm BLACK 1 x 70 mm M8 8Nm B2 M8 20Nm C 4500 mm RED 1 x 70 mm M8 8Nm B2 M8 20N...

Page 66: ...66 EN BATTERY CABINET ITYS PRO 10 20 kVA MASTERYS 10 160 kVA Ref IOMXXXABXX00 EN 01 8 Nm C cables TX20 1 2 3 4 5 C cables M10 25 Nm A B cables 8 Nm TX20...

Page 67: ......

Page 68: ......

Page 69: ...1MBFxxxxxxx4Mxx MASTERYS 160 kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...

Page 70: ...0 20 kVA MASTERYS 10 160 kVA Ref IOMXXXABXX00 EN 01 16 CONNECTIONS 1MBFXXXXXXX4MXX NOTE Before carrying out any operations on the unit read the Safety standards chapter carefully Do not remove side pa...

Page 71: ...ON A cables 1 2 N B B N LOCKING CABLE CLAMP CABLE CABLE LENGTH COLOUR CABLE SECTION UPS 1MBFxxxxxxx4Mxx B M8 8Nm A 4500 mm RED 1 x 95 mm N N M8 8Nm BLUE 1 x 50 mm B M8 8Nm 4500 mm BLACK 1 x 95 mm Clos...

Page 72: ...72 EN BATTERY CABINET ITYS PRO 10 20 kVA MASTERYS 10 160 kVA Ref IOMXXXABXX00 EN 01 TX20 1 A B cables 28 Nm TX20 2 3...

Page 73: ......

Page 74: ......

Page 75: ...1MBFxxxxxxx2Mxx 1MBFxxxxxxx0Mxx MASTERYS 160 kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...

Page 76: ...MASTERYS 10 160 kVA Ref IOMXXXABXX00 EN 01 17 CONNECTIONS 1MBFXXXXXXX2MXX 1MBFXXXXXXX0MXX NOTE Before carrying out any operations on the unit read the Safety standards chapter carefully 1 2 TX20 Do n...

Page 77: ...LAMP CABLES CABLE LENGTH COLOUR CABLE SECTION UPS 1MBFxxxxxxx2Mxx 1MBFxxxxxxx0Mxx B M8 8Nm A 4500 mm RED 1 x 95 mm N N M8 8Nm BLUE 1 x 50 mm B M8 8Nm 4500 mm BLACK 1 x 95 mm M8 8Nm B2 M8 20Nm B 5000 m...

Page 78: ...78 EN BATTERY CABINET ITYS PRO 10 20 kVA MASTERYS 10 160 kVA Ref IOMXXXABXX00 EN 01 B cables 28 Nm TX20 1 2 3 4 5 B cables M10 25 Nm A cables 28 Nm TX20...

Page 79: ...PRO 10 20 kVA MASTERYS 10 160 kVA Ref IOMXXXABXX00 EN 01 18 TEMPERATURE SENSOR 1MBFxxxxxxx2Mxx 1MBFxxxxxxx0Mxx B B N B B N 1MBFxxxxxxx2H 1 1MBFxxxxxxx20xx 1MBFxxxxxxx4Hxx 1MBFxxxxxxx2Hxx 1MBFxxxxxxx4M...

Page 80: ...ronment Mechanics options Tripping sys tem IP31 IP32 Back base 2 Lateral cov ers Spill container ITYPxxxxxxx2Pxx 1MBFxxxxxxx4Pxx 1MBFxxxxxxx2Fxx 1MBFxxxxxxx4Fxx 1MBFxxxxxxx2H 1 1MBFxxxxxxx20xx 1MBFxxx...

Page 81: ...81 EN BATTERY CABINET ITYS PRO 10 20 kVA MASTERYS 10 160 kVA Ref IOMXXXABXX00 EN 01 19 3 IP32 Dimensions WxDxH 1012 x 1077 x 2110 mm 19 4 BACK BASE...

Page 82: ...82 EN BATTERY CABINET ITYS PRO 10 20 kVA MASTERYS 10 160 kVA Ref IOMXXXABXX00 EN 01 19 5 2 LATERAL COVERS 19 6 SPILL CONTAINER...

Page 83: ...can leak into the groundwater and get into the food chain damaging health and wellbeing Depleted batteries are considered as toxic waste When battery replacement becomes necessary only give rundown b...

Page 84: ...on IP31 option IP32 Operating temperature 0 40 C 15 25 C recommended for longer battery life Ambient storage and transport temperature 2 5 C to 40 C max recommended 25 C Relative humidity condensation...

Page 85: ...10 160 kVA Ref IOMXXXABXX00 EN 01 22 APPENDIX 22 1 PLAN 1 FLOOR FIXING ITYPxxxxxxx2Pxx 1MBFxxxxxxx4Pxx 2Fxx 4Fxx A A 600 835 798 635 512 100 63 82 44 9 5 1MBFxxxxxxx2H 1 2Hxx 20xx 4Hxx 4Mxx 2Mxx 0Mxx...

Page 86: ...10 20 kVA MASTERYS 10 160 kVA Ref IOMXXXABXX00 EN 01 22 2 PLAN 2 DIMENSIONS ITYPxxxxxxx2Pxx 1MBFxxxxxxx4Pxx 2Fxx 4Fxx FRONT VIEW LATERAL VIEW REAR VIEW 1MBFxxxxxxx2H 1 2Hxx 20xx 4Hxx 4Mxx 2Mxx 0Mxx FR...

Page 87: ......

Page 88: ...nce 80countries where our brand is distributed 8production sites q France x3 q Italy q Tunisia q India q China x2 27subsidiaries q TRSQ KH q DKFHTL q GHM q Q MBD q DQL MX q MCH q S KX q DSGDQK MCR q N...

Reviews: