30
MASTERYS
BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
7. CONNECTIVITY AND COMMUNICATION OPTIONS
Intervention of the ESD input switches off the UPS output.
To restore the UPS to operation:
• Close the ESD contact on ‘In 1’ on the ADC board.
• Send the Alarms Reset command.
• Run the Automatic Start Procedure
7.3. REMOTE MIMIC PANEL
This device monitors and interacts with the UPS through a serial link RS 485 (maximum distance of 175 m) 25 m cable supplied
as standard and 50 m cable available as an option.
7.4. NET VISION LAN/WEB INTERFACE
NET VISION
is a communication and management interface to be installed in the UPS slot designed for business networks. The
UPS behaves exactly like a networked peripheral, it can be managed remotely and allows the shutdown of network workstations.
NET VISION
allows a direct interface between the UPS and LAN network avoiding dependence on the server and support SMTP,
SNMP, DMCP and many other protocols. It interacts via the Web browser.
Please note that two Net Vision cards cannot be connected simultaneously.
7.5. PROFIBUS
INTERFACE
The externally mounted PROFIBUS adapter allows UPS models to be connected to a Profibus network.
7.6. SOFTWARE
OPTIONS
A large number of SW solutions can be adopted on MASTERYS BC thanks to its advanced communication facilities. These solu-
tions have been specially designed for the efficient management of power protection devices.
Visit
www.socomec.com
and click on
DOWNLOAD
then
SOFTWARE
to find the communication software which is suitable for
your requirements.
Description of signals
Message on the mimic panel
Description
General Alarm
‘General Alarm’ contact output
No alarm
C1
NO1
NC1
‘General Alarm’ active
C1
NO1
NC1
Battery Low or Imminent stop
Battery low voltage and imminent shutdown contact output
Supply from GenSet
Generator ready signal input
Power safe plug 1
Non privileged load 1 command output activated by overload or loss of redundancy
Power safe plug 2
Non privileged load 1 command output activated by battery discharging
Power safe plug 3
Non privileged load 1 command output activated by low battery
Management of energy consumption
Input for the battery to help providing energy in the event of peak consumption
ESD activation
Shutdown for ESD contact outpu
Overheating
Internal overheating contact output
Overload/Loss of redundancy
Overload / loss of redundancy contact output