23
CPSS Emergency MASTERYS EM
10 to 80 kVA - Ref.: IOMMASELXX03-GB 00
PRESENT CONFIGURATIONS menu
A
Parameter
Description
Allowed values
LANGUAGE SELECTION
Selects the required language
DE-EN-ES-FR-IT, other lan-
guages on request
•
NUMBER OF MODULES
Only appears with parallel systems.
Indicates the number of UPSs in the system.
1-2
•
REDUNDANCY LEVEL
Only appears with parallel systems.
Indicates the number of redundant UPSs.
FROM 0 TO THE NUMBER
OF MODULES LESS ONE
•
OUTPUT VOLTAGE
Sets the required output voltage value.
208/220/230/240
•
OUTPUT FREQUENCY
Sets the required output frequency value.
50/60
•
CONVERTER
Sets whether or not the UPS has to operate as a fre-
quency converter.
WARNING!
Set only on UPS with mains power (MAINS) and
auxiliary mains (AUX MAINS) separate and with
the auxiliary mains (AUX MAINS) disconnected!
Do not set on UPS with common mains lines as
it could damage the load!
YES/NO
•
AUTO ON
Sets whether or not the UPS has to restart automatical-
ly after shutdown due to minimum battery level.
YES/NO
BATTERY AVAILABLE
Indicates whether the batteries are present
YES/NO
BATTERY TEMP. PROBE
Indicates if the battery sensor is present
ENABLE/DISABLE
•
BATTERY TYPE
Selects the type of batteries used
SEALED, OPEN VENT, NI-
CD
•
BATTERY RECHARGE
Selects the type of recharge required
AUTO, MAINTENANCE, 2
LEVELS, INTERMITTENT
•
BATTERY CAPACITY
Sets the battery capacity in Ah.
6.60 - 1,000 (x number of
UPS)
•
BATTERY ELEMENTS
Indicates the number of elements in series in a branch.
114-132
•
BATTERY RECHARGE TEMP
COMPENSATION
Sets the recharge voltage compensation value ac-
cording to the battery temperature (not present with
external battery cabinets.
YES/NO
•
BACKFEED TYPE
Sets the type of backfeed protection.
DISABLE
BY-PASS-INPUT ALONE
BY-PASS-INPUT COMMON
•
BATTERY TEST
TEST EVERY XX DAYS
Sets the frequency rate of the battery test in days (zero
= do not perform the test).
0-180
•
LAN STATIC IP
XXX . XXX . XXX .XXX
Sets the static IP address of the LAN
255.255.255.255
•
SERIAL LINK JBUS
SLAVE NUMBER
Sets the mimic panel jbus node
1-15
DATE AND TIME
Sets the date and time
DD/MM/YY HH:MM
•
EXTENDED COMMAND
Enables/Disables the mimic panel extended commands
YES/NO
•
REMOTE COMMAND
Enables/disables the remote commands
YES/NO
BUZZER
Enables/Disables the buzzer
YES/NO
LCD CONTRAST
Sets the LCD display contrast
0/100
•
STATISTICS PERIOD
Indicates the time in weeks for the calculation of statistics 1-10
7. MENU
YOUR CONNECTION TO SAFETY
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• info@thiele-kg.de
• www
.thiele-kg.de
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• info@thiele-kg.de
• www
.thiele-kg.de
YOUR CONNECTION TO SAFETY
klick to
www
u-s-v
YOUR CONNECTION TO SAFETY
klick to
www
ACDC-DCDC
YOUR CONNECTION TO SAFETY
klick to
www
SYSTEME
YOUR CONNECTION TO SAFETY
klick to
www
CONTACT
YOUR CONNECTION TO SAFETY
klick to
www
CALLBACK