25
CPSS Emergency MASTERYS EM
10 to 80 kVA - Ref.: IOMMASELXX03-GB 00
8. OPERATING PROCEDURES
8.1. UPS 10 TO 40 KVA
SWITCHING ON
• Set switch
Q1
and/or the external batteries switches to position
1
(battery circuit closed).
• Apply voltage to the UPS.
• Set switch
Q2
to position
1
(input mains ON).
• Wait for the mimic panel to start up.
• Activate the
START PROCEDURE
from the
COMMANDS
menu on the mimic panel.
• Set disconnecting switch
Q6
to position
1
(continuous output).
• The load is now powered and protected by the UPS.
SWITCHING OFF
Shutdown interrupts the power supply to the load and stops the UPS and the battery charger.
• Activate the
STOP PROCEDURE
from the
COMMANDS
menu on the mimic panel, wait approx. 2 minutes for shutdown (the
controlled shutdown of any servers is managed via the shutdown software).
• Set disconnecting switch
Q6
to position
0
(inverter in output OFF).
• Set switch
Q1
and/or battery switches to position
0
(battery circuit open).
• Set switch
Q2
to position
0
(input mains OFF).
BYPASS OPERATIONS
Switching onto manual bypass
Switching onto manual bypass creates a direct connection between the UPS input and output, completely excluding the equipment
control element.
This operation is performed in the event of standard maintenance on the equipment, so as not to remove the power supply from
the load, or in the event of a serious failure while waiting for the equipment to be repaired.
• From the mimic panel set the
HIGH EFF. MODE
command from the
IMMEDIATE COMMANDS
menu.
• Wait for the command to be executed (bypass line on the M1 display on). If this does not take place, suspend the operation (the
auxiliary mains is not suitable for the load).
• Set disconnecting switch
Q6
to position
2
.
• Set switch
Q1
and/or battery switches to position
0
(battery circuit open).
• Open the switch
Q2
.
If there is an external manual bypass carry out the procedure described above before activating this switch.
Return to normal mode
• Set switch
Q2
to position
1
(input mains ON).
• Set switch
Q1
and/or the external battery switches to position
1
(battery circuit closed).
• Activate the start procedure from the commands menu on the mimic panel.
• From the mimic panel set the
HIGH EFF. MODE
command from the
IMMEDIATE COMMANDS
menu.
• Check that alarm A06 is not present (if the alarm is present, resolve the problem before continuing).
• Set disconnecting switch
Q6
to position
1
(inverter in output ON).
If there is an external manual bypass, put the switch to position OFF.
• From the mimic panel set the
NORMAL MODE
command from the
IMMEDIATE COMMANDS
menu.
YOUR CONNECTION TO SAFETY
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• info@thiele-kg.de
• www
.thiele-kg.de
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• info@thiele-kg.de
• www
.thiele-kg.de
YOUR CONNECTION TO SAFETY
klick to
www
u-s-v
YOUR CONNECTION TO SAFETY
klick to
www
ACDC-DCDC
YOUR CONNECTION TO SAFETY
klick to
www
SYSTEME
YOUR CONNECTION TO SAFETY
klick to
www
CONTACT
YOUR CONNECTION TO SAFETY
klick to
www
CALLBACK