31
CPSS Emergency MASTERYS EM
10 to 80 kVA - Ref.: IOMMASELXX03-GB 00
10. STANDARD FEATURES AND OPTIONS
10.2. STANDARD WEBPAGES
It is possible to remotely monitor the UPS using an Internet browser from a PC, through a standard ethernet connection (tested with
Windows XP Service Pack 3 on Internet Explorer 8, Google Chrome 17.0 and Mozilla Firefox 9.0 with JavaScript enabled).
Activation
Perform the following operations to activate the monitoring system:
1. Connect the UPS to the LAN network.
Check if the
WEB SERVER
service is
ENABLED
.
The configuration is in
MAIN MENU > SETTINGS > CONNECTIVITY > SERVICES > NETWORK
.
2A. If the DHCP service is enabled on your local network the network parameters assigned to the UPS can be seen in the
MAIN
MENU > SETTINGS > CONNECTIVITY > PERIPHERALS > NETWORK PARAMETERS
menu.
2B. If the DHCP service is not enabled on the local network:
- enter the
MAIN MENU > SETTINGS > CONNECTIVITY > PERIPHERALS > NETWORK PARAMETERS
menu
- disable the
DHCP
and save
- set the device network parameters according to those of the network and save.
3. Once these operations have been completed you should see the network icon in the main view
.
It will now be possible to open your web browser and type the device IP address (i.e.: http://192.168.0.11).
Note: the default
HTTP
port is 80 but it can be changed in the
MAIN MENU > SETTINGS > CONNECTIVITY > PERIPHERALS
> NETWORK TCP PORTS
menu on the display.
Via the webpages it is possible to monitor the UPS and set the different functions available via the network, such as e-mail notifica-
tions, network parameters, web password and the UPS solution.
All settings pages are password protected.
The login is
admin
and the default password is
public
(lower case only). The password can be changed in the
SETTINGS >
PASSWORD
web pages or on the HMI menu:
MAIN MENU > SETTINGS > PREFERENCES > PASSWORDS > WEB PASSWORD.
UPS monitoring
The main page gives the current view of UPS status. The view is refreshed automatically.
You can click on the Input, Battery, Output, Bypass symbols to access the relevant measurements.
Using the
UPS MONITOR
link on the menu it is possible to return to the UPS synoptic.
In the case of a parallel system a line is added at the bottom of the display showing the current status of each unit.
YOUR CONNECTION TO SAFETY
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• info@thiele-kg.de
• www
.thiele-kg.de
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• info@thiele-kg.de
• www
.thiele-kg.de
YOUR CONNECTION TO SAFETY
klick to
www
u-s-v
YOUR CONNECTION TO SAFETY
klick to
www
ACDC-DCDC
YOUR CONNECTION TO SAFETY
klick to
www
SYSTEME
YOUR CONNECTION TO SAFETY
klick to
www
CONTACT
YOUR CONNECTION TO SAFETY
klick to
www
CALLBACK