34
CPSS Emergency MASTERYS EM
10 to 80 kVA - Ref.: IOMMASELXX03-GB 00
Intervention of the ESD input switches off the UPS output.
To restore the UPS to operation:
• Close the ESD contact on ‘In 1’ on the ADC board.
• Send the Alarms Reset command.
• Run the Automatic Start Procedure
10.4. ADC CARD WITH TEMPERATURE SENSOR
Inputs and outputs of this card have the same functions as the ADC card, except the third input (IN3).
This one is dedicated to the external battery temperature probe in all confi gurations.
This function has to be set on the control panel.
WARNING!
Note that two ADC cards with temperature probe cannot be connected simultaneously.
10.5. ACS PCB
Synchronises UPS output with an external power source (another UPS, even of a diff erent brand, generator or transformer).
10.6. POWER SHARE (UPS 60 TO 80 kVA ONLY)
General information
The POWER SHARE function can be used to programme the supply of energy to the loads connected to the POWER SHARE
terminal board via the mimic panel or the NET-VISION option (Network Integrator).
The loads powered from this plug may have a lower priority than the privileged applications connected to the main plug and may
be excluded in critical situations.
Operating modes
•
Standard
In standard confi guration, the load connected to the POWER SHARE plug is disconnected if one of the following conditions is
verifi ed:
- Mains failure >10 seconds and load rate > 85%.
- Mains failure >30 seconds and 'battery low' condition
- In the presence of mains with overload > 15 seconds
Description of signals
Message on the mimic panel
Description
General Alarm
‘General Alarm’ contact output
No alarm
C1
NO1
NC1
‘General Alarm’ active
C1
NO1
NC1
Battery Low or Imminent stop
Battery low voltage and imminent shutdown contact output
Supply from GenSet
Generator ready signal input
Power safe plug 1
Non privileged load 1 command output activated by overload or loss of redundancy
Power safe plug 2
Non privileged load 1 command output activated by battery discharging
Power safe plug 3
Non privileged load 1 command output activated by low battery
Management of energy consumption
Input for the battery to help provide energy in the event of peak consumption
ESD activation
Shutdown for ESD contact outpu
Overheating
Internal overheating contact output
Overload/Loss of redundancy
Overload / loss of redundancy contact output
YOUR CONNECTION TO SAFETY
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• info@thiele-kg.de
• www
.thiele-kg.de
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• info@thiele-kg.de
• www
.thiele-kg.de
YOUR CONNECTION TO SAFETY
klick to
www
u-s-v
YOUR CONNECTION TO SAFETY
klick to
www
ACDC-DCDC
YOUR CONNECTION TO SAFETY
klick to
www
SYSTEME
YOUR CONNECTION TO SAFETY
klick to
www
CONTACT
YOUR CONNECTION TO SAFETY
klick to
www
CALLBACK