37
CPSS Emergency MASTERYS EM
10 to 80 kVA - Ref.: IOMMASELXX03-GB 00
10.12.
PROTECTION ON A UPS WITHOUT AUXILARY MAINS SUPPLY
Activating UPS protection: access the
MAIN MENU > SETTINGS > UPS SETTINGS > BACKFEED
and set the
BACKFEED
TYPE
parameter to
COMMON MAINS
.
Layout
A
UPS
L1
Q1
L2
L3
N
T1
B
M1
L1
L2
L3
N
XB1
BKF card
10.12-1
UPS 3/3 without separate auxiliary supply.
Key
A
Distribution
panel
B
Remote coil switch
L1-L2-L3-N
Input power source
M1
Input power terminal board
Q1
Input power switch
T1
Remote
switch
1
XB1
Connector on BKF PCB
1
Remote switches - rated current
Model
T1
10 3/1
32 A AC1
15 3/1
32 A AC1
20 3/1
45 A AC1
10 3/3
32 A AC1
15 3/3
32 A AC1
20 3/3
45 A AC1
30 3/3
60 A AC1
40 3/3
90 A AC1
60 3/3
125 A AC1
80 3/3
140 A AC1