39
CPSS Emergency MASTERYS EM
10 to 80 kVA - Ref.: IOMMASELXX03-GB 00
11. WARNING AND TROUBLESHOOTING
UPS warnings
Warning
Cause
Remedy
A01
BATTERY ALARM
Failure or problem on the battery circuit. Check the battery switch is closed.
A18
OVERLOAD OFF INV
Reduce the load rate applied to the
UPS and reset the alarms.
A20
WRONG CONFIG.
Error in the configuration parameters
contact the support service.
A30
OVERLOAD STOP
Reduce the load rate applied to the
UPS and reset the alarms.
A42
REMOTE SERVICE ALARM
This alarm indicates that a critical fault
has occurred on the UPS. Where a
maintenance contract is in place the
procedure for analysing the UPS via
remote connection will be automatically
activated by your service centre provider.
A44
SERVICE CHECK
The equipment has to undergo regular
checks by the support service in order to
ensure optimum performance and efficiency.
If the Scheduled Inspection signal appears
on the mimic panel, the equipment should
be inspected by a suitably trained technician.
A59
BATT.CIRC. OPEN
Battery switch open.
A60
FAN FAILURE
Fault in the ventilation system
check the air inlet at the front and the air outlet
at the back of the UPS are not obstructed.
YOUR CONNECTION TO SAFETY
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• info@thiele-kg.de
• www
.thiele-kg.de
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• info@thiele-kg.de
• www
.thiele-kg.de
YOUR CONNECTION TO SAFETY
klick to
www
u-s-v
YOUR CONNECTION TO SAFETY
klick to
www
ACDC-DCDC
YOUR CONNECTION TO SAFETY
klick to
www
SYSTEME
YOUR CONNECTION TO SAFETY
klick to
www
CONTACT
YOUR CONNECTION TO SAFETY
klick to
www
CALLBACK