6
CPSS Emergency MASTERYS EM
10 to 80 kVA - Ref.: IOMMASELXX03-GB 00
2. LOCATION AND HANDLING REQUIREMENTS
2.1. LOCATION
REQUIREMENTS
Install the unit in an equipment room where only skilled technicians have access. The room must be:
• of a suitable size;
• free from conductive, inflammable and corrosive items;
• not exposed directly to sunlight.
The floor must support the weight of the unit and guarantee its stability.
The unit is designed for indoor non-air-conditioned rooms only.
For information regarding ambient temperature, dimensions and weights refer to the Technical Specification chapter.
A cooling system may be required in order to maintain the ambient temperature values.
To position the unit correctly see the diagrams below.
All packaging must be recycled in compliance with existing legislation in the country where the system is installed.
UPS OR O
THER
C
ABINET
UPS OR O
THER
C
ABINET
UPS OR O
THER
C
ABINET
UPS
40 cm
1,5 m
2.1-1
UPS
40 cm
1,5 m
20 cm
20 cm
2.1-2
2.2. HANDLING
• The packaging guarantees the stability of the unit during shipping and physical transfer.
• The unit must remain in a vertical position during all shipping and handling operations.
• Ensure that the floor is strong enough to support the weight of the unit.
• Carry the packaged unit as close as possible to the installation site.
• The unit has wheels that can be used to move it for short distances.
WARNING! HEAVY WEIGHT!
Move the unit using a fork lift truck taking the utmost caution at all times.
The unit must be handled by at least two people. They must stand at the sides of the UPS with respect to the direc-
tion of movement.
Do not move the unit by putting pressure on the front door.
When moving the unit on even slightly sloping surfaces, use the locking equipment and braking devices to ensure
that the unit does not fall over.
When the equipment is transferred from a cold to a warm place wait approx. two hours before putting the unit into
operation.
CAUTION IF DAMAGED.
If the unit is found to be damaged externally or internally, or any of the accessories are damaged or missing, contact
SOCOMEC.
2.1-3
Only for raised fl oor
A. power cables
B. control cables
20 cm
90°
A
A
B
B
YOUR CONNECTION TO SAFETY
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• info@thiele-kg.de
• www
.thiele-kg.de
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• info@thiele-kg.de
• www
.thiele-kg.de
YOUR CONNECTION TO SAFETY
klick to
www
u-s-v
YOUR CONNECTION TO SAFETY
klick to
www
ACDC-DCDC
YOUR CONNECTION TO SAFETY
klick to
www
SYSTEME
YOUR CONNECTION TO SAFETY
klick to
www
CONTACT
YOUR CONNECTION TO SAFETY
klick to
www
CALLBACK