MASTERYS BC
from 15 to 20 kVA
29
ENGLISH
6
MIMIC PANEL
6.1.3.5 “Service” menu
This is used to change the configuration parameters, insert the warranty activation code and display the service
code.
“UPS SETTINGS” menu
This is used to change the configuration parameters. Access is via the password
MAST
which is keyed in by
using the
UP
e
DOWN
keys and
ENTER
to go on to the next letter.
UPS SETTINGS menu
Parameter
Description
Allowed values
SET OUTPUT VOLTAGE
Sets the required output voltage value
208/220/20/240 V
SET OUTPUT FREQUENCY Sets the required output frequency value
50/60 Hz
SET MODE CONVERTER
Sets whether the UPS has to operate as a frequency converter
YES/NO
WARNING!
Set only on UPS with mains power (MAINS) and auxiliary mains (AUX MAINS) separated
and with the auxiliary mains (AUX MAINS) disconnected!
Do not set on UPS with common mains lines as it could damage the load!
SET MODE AUTORESTART Sets whether the UPS has to restart automatically after shutdown YES/NO
due to minimum battery
SET BATTERY AVAILABLE
Set if battery are present
YES/NO
if YES:
-
SET BATTERY TYPE
Selects the type of batteries used
Sealed
- SET BATTERY CAPACITY
Sets the battery capacity in Ah
9,5 – 1000 Ah
- SET CHARGER TYPE
Selects the type of recharge required
Auto, Float, int.
- SET BATTERY ELEMENTS
Set the number of battery elements
90 - 108
- SET BATT_TEST PERIOD
Sets how often to perform the battery test
0, 0, 60, 90, 120,150.180
(zero do not perform the test) in days
SET BACKFEED TYPE
Sets the type of backfeed protection
Disable , 1.BYPASS ,
2.ByPass-Input alone,
.ByPass-Input common
SERIAL LINK
Inserts the serial communication parameters:
Serial Link Baud Rate
1200/2400/4800/9600/14.4
Serial Link Parity
odd/even/none
Serial Link Bit Number
8-9
Serial Link Stop Bits
0-1
When the data is confirmed, the serial connection automatically changes the configuration
without having to switch off the UPS.
JBUS SETTING SLAVE NR.
Sets the mimic panel jbus node
1/2
When the data is confirmed, the serial connection automatically changes the configuration
without having to switch off the UPS.
DATE SETUP
Sets the date
GG/MM/AA
TIME SETUP
Sets the time
HH:MM
SYN EXT CMDS ENABLED Enables/Disables the mimic panel extended commands
YES/NO
REMOTE CMDS ENABLED Enables the transmission of commands from external systems
YES/NO
SET BUZZER
Enables/Disables the buzzer
YES/NO