MASTERYS BC
from 15 to 20 kVA
40
IT
ALIANOENGLISH
10
OPTIONS
10.1 ADC CARD.
This card can be configured to control up to four outputs that are normally closed or normally open and up to
three digital inputs. A maximum of two cards can be installed on each unit. The card must be inserted in slot
S1 or S2 (see paragraph 5.1).
10.1-1
A
2
3
4
1
OU
T
OUT
0 1 2 P3
C2
NO2
NC2
IN1-
IN1+
IN3-
IN3+
C3
NO
3
NC3
C1
NO
1
NC1
IN1-
IN1+
IN2-
IN2+
C4
NO
4
NC4
Up to four operating modes can be selected using the two DIP switches 1 or 2.
• The filter level indicates:
1 immediate activation (1 second minimum communication time) - 2 10 s delay - 3 0 s delay.
Mode 1 - STANDARD configuration
Position
IN/OUT
Description
Filter
dip1 dip2
level
OFF OFF
Out 1
General Alarm
2
OFF OFF
Out 2
Battery discharging
OFF OFF
Out
Battery low or
2
imminent stop
OFF OFF
Out 4
UPS on by-pass
2
OFF OFF
In 1
*
E.S.D.
1
OFF OFF
In 2
Supply from GenSet
1
OFF OFF
In
Isolation controller
2
Mode 2 - POWER SAFE configuration
Position
IN/OUT
Description
Filter
dip1 dip2
level
ON OFF
Out 1
General Alarm
2
ON OFF
Out 2
Power safe plug 1
2
ON OFF
Out
Power safe plug 2
2
ON OFF
Out 4
Power safe plug
2
ON OFF
In 1
*
E.S.D.
1
ON OFF
In 2
Supply from GenSet
1
ON OFF
In
Management of
1
energy consuption
Mode 3 - SAFETY configuration
Position
IN/OUT
Description
Filter
dip1 dip2
level
OFF ON
Out 1
General Alarm
2
OFF ON
Out 2
E.S.D. activation
1
OFF ON
Out
Battery low or
2
imminent stop
OFF ON
Out 4
E.S.D. activation
1
OFF ON
In 1
*
E.S.D.
1
OFF ON
In 2
External alarm A9
2
OFF ON
In
External alarm A40
2
Mode 4 - ENVIRONMENTAL configuration
Position
IN/OUT
Description
Filter
dip1 dip2
level
ON ON
Out 1
General Alarm
2
ON ON
Out 2
Over-heating
2
ON ON
Out
Overload /
2
Loss of redundancy
ON ON
Out 4
External alarm In2
2
ON ON
In 1
*
E.S.D.
1
ON ON
In 2
External alarm A9
2
ON ON
In
External alarm A40
2
*
if the external E.S.D. button is not used, always insert a jumper to short circuit input IN 1 (Figure 10.1-1).
OUT1
IN2
OUT4
OUT2
OUT3
IN3
DIP1 2
IN1