MASTERYS BC
from 15 to 20 kVA
42
IT
ALIANOENGLISH
OPTIONS
10
10.3 REMOTE MIMIC PANEL.
This device monitors and interacts with the UPS through
a serial link RS 485 (maximum distance of 175 m) 25 m
cable supplied standard; 50 m cable available as an op-
tion). Connect the RS485 cable supplied onto port C1
of the unit (see figure 5.1-1). Refer to the relevant user
manual for instructions on how to use the device.
10.4 POWER SHARE.
10.4.1 General information.
The POWER SHARE function can be used to pro-
gramme the supply of energy to the loads connected to the POWER SHARE terminal board via the mimic panel
or the NET-VISION option (Network Integrator).
The loads powered from this plug may have a lower priority than the privileged applications connected to the
main plug and may be excluded in critical situations.
10.4.2 Operating modes.
WARNING!
Changing the configuration from “Standard” to “Emergency lights”
must
be carried out
only
by
specially trained SOCOMEC UPS staff.
• Standard.
In standard configuration, the load connected to the POWER SHARE plug is disconnected if one of the follow-
ing conditions is verified:
- Mains failure >10 seconds and load rate > 85%.
- Mains failure >0 seconds and “battery low” condition
- In the presence of mains with overload > 15 seconds
• “Emergency lighting”.
In an emergency lighting configuration, the load connected to the POWER SHARE plug operates with inverse
logic, i.e. it is connected if the following condition is verified: Mains power is not present.
According to the EN 50171 standard, the time taken to activate the power share plug is
within 0.5 seconds.
On return of the nominal mains parameters, the plug operating conditions are restored.
If the UPS is out of service, the power share plug nevertheless powers the load connected to
it by operating in permanent configuration.
THE LOAD CONNECTED TO THE POWER SHARE PLUG IS ALWAYS POWERED, REGARDLESS OF
THE CONFIGURATION SELECTED.
Maximum current that can be drawn from the power share terminals: 16 A 250 Vac Ac -phase.
10.3-1