MASTERYS BC
from 15 to 20 kVA
46
IT
ALIANOENGLISH
TECHNICAL SPECIFICATIONS
11
Models
15
15
20
20
Input/Output phases
/1
/
/1
/
Standards
15
15
20
20
Safety
(EN) IEC 62040-1-1, (EN) IEC 60950-1-1*
Type and performance
(EN) IEC 62040- (VFI-SS-111)
EMC
IEC 62040-2, EN 50091-2
Product certification
Protection level
IP20 (compliant with 60529), IP21 on request
*TÜV tested
Environment
15
15
20
20
Operating temperature
0÷40 °C (15÷25 °C recommended for longer battery life)
Storage temperature
-5÷45 °C
Relative humidity
0÷95% condensation-free
Max. altitude
1.000 m (.00 ft) without derating; .000 m (10.000 ft) max
Acoustic noise (dB)
< 55
Required cooling capacity (m
/h)
546
Dissipated power max (W)
1.187
1.187
1.78
1.78
Dissipated power (BTU/h)
4.051
4.051
5.9
5.9
Electrical specifications - Input
15
15
20
20
Mains voltage
400 V ±20% (up to -5% @70% of nominal load)
(three phase + neutral)
Input frequency
50/60 Hz ±10%
Input power factor
0,97 (three phase)
THDI
< 10%
Electrical specifications - Output
15
15
20
20
Output voltage
20 V single phase (selectable: 220/240 V) ±1%
(three phase + neutral)
400 V three phase (selectable 60*/80/415 V) ±1%
Frequency
50/60 Hz ±2% (from 1% to 8% if generator is used)
Automatic bypass
nominal output voltage ±15%
(from 10% to 20% selectable if generator is used)
Nominal power (kW)
12
12
16
16
Overload on mains power supply
125% 10 minutes
Crest factor
:1
Voltage distortion
1% with linear load
*@ 208 V Pout = 90% Pnom