17
MODULYS GP Green Power 2.0
range from 25 to 200 kVA - Ref.: IOMMODGPXX05-GB 01
ENGLISH
5. CONNECTIONS
5.3-1
5.3. EXTERNAL BATTERY CONNECTION
NOTE!
For further information refer to the battery cabinet manual.
• Remove the plastic terminal block protection.
• Connect the protective earth (PE) cable.
• Connect the cables between the UPS terminals and the battery cabinet terminals.
WARNING!
Strictly observe:
- the polarity of each individual string (refer to the figure below);
- the cable cross section (refer to ‘Electrical requirements’ chapter).
WARNING!
Cabling errors with inversion of battery polarity may cause permanent damage to the equipment.
Reassemble the plastic terminal block protection.
+
N
-
+B
N
-B
UPS
BATTERY CABINET
NOTE!
When battery cabinets not supplied by Socomec are used the installer is responsible for:
- checking electrical compatibility;
- checking the presence of appropriate protective devices (fuses and switches that ensure the cables are protected
from the UPS to the battery cabinet).
Once the UPS is switched on – before closing the battery switches – check the battery parameters on the control
panel menu. For further information, refer to ‘Menu’ chapter.
NOTE!
Not all battery/capacity combinations are available.