10
MODULYS Green Power
- Ref.: IOMMODGPXX01-GB 00
3. UNPACKING
Installation Environment and Position
3.5.
Handling Safety
3.5.1.
1. The UPS is equipped with casters so that you can roll the UPS in a short distance to the desired location. During unpacking
process, be sure to make full use of manpower and a suitable machine (such as stacker) with sufficient capacity to carefully move
the UPS.
Please pay extremely close attention while unbolting the UPS from the shipping pallet. Prevent any accident
resulting from unexpected move.
2. Casters are only suitable for moving on even surface. Avoid moving the UPS on bumpy route, because this may cause damage
of UPS or tip-over accident.
3. Push the UPS from either front or rear side otherwise could cause tip-over accident.
4. When the UPS needs a long-distance movement, make use of a suitable machine but not casters of the UPS.
UPS Position
3.5.2.
1. Position the UPS by suitable machine.
2. Ensure that the UPS is positioned at a suitable floor which can sustain
for the weight.
3. After positioning the UPS, ensure to push C (Stop) to “ON” until strictly
fastened and adjust leveler to the floor.
4. Attach the balance supporter to the UPS with bolts.
The UPS may topple over under unexpected conditions withoug balance supporter. Be sure to mount two balance
supporters on both sides of the UPS for safety reasons.
3.5.2-1
3.5.2-2
Balance
Supporter
A
B
C
A : Leveler
B : Caster
C : Stop
002 DR
WMODGP-XX
003 DR
WMODGP-XX
Summary of Contents for MODULYS Green Power