MODULYS Green Power
- Ref.: IOMMODGPXX01-GB 00
ENGLISH
7. MIMIC PANEL
Item
Symbol
Description
Condition
1
Load on bypass, Eco-mode or
Maintenance bypass closed.
Steady
Automatic bypass alarm.
Flashing
2
Input rectifier active.
Steady
Input rectifier general alarm.
Flashing
3
Battery OK
Steady
Battery alarm.
Flashing
4
Inverter on
Steady
Inverter general alarm.
Flashing
5
Output voltage present.
Steady
6
Input mains OK.
Steady
Input mains alarm.
Flashing
7
Inverter on.
Steady
8 ÷13
Module present. Each module: 20 kVA
Steady
Module general alarm.
Flashing
14
Load present.
Steady
Overload.
Flashing
15
Output load indicator.
Steps of 10%
16
Activation code alarm.
Steady
General alarm.
Flashing
17
Periodic maintenance alarm/warning.
Flashing
18
LAN connection ready (cable connected).
Steady
Meaning of the luminous bar.
7.3.
The luminous bar (figure 7.1-1) provides an immediate indication of the condition of the power supply to the load:
General description
Colour
UPS conditions
Output power supply not present or
imminent shutdown
RED flashing
Imminent stop: the load will be
disconnected in 2 minutes.
Battery low when load on Battery Mode.
RED
Load is not supplied.
Output power supply present but unsta-
ble or temporary
YELLOW flashing
The UPS switches off by remote
shutdown only.
UPS in stand by
YELLOW
Load on by-pass.
Load on battery Mode
Redundacy lost
Output power supply available and
regular by inverter.
GREEN flashing
Battery test in progress
GREEN
Load on inverter
Meaning of ideograms